Skip to main content
Schneider Electric LC1D65008M7

Schneider Electric LC1D65008M7 TeSys Deca Contactor, 80 A AC

MPNLC1D65008M7
Active

Schneider Electric, TeSys Deca, 4-pole contactor LC1D65008M7, 80 A AC-1 resistive load, AC coil 50/60 Hz, 4.9 in depth.

$765.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1D65008M7 key specifications
ParameterValue
Range of productTeSys Deca
Control circuit typeAC 50/60 Hz
Product or component typeContactor
Climatic withstandIACS E10 exposure to damp heat
Coil voltage220 V AC 50/60 Hz
VoltagePower circuit 600 V CSA Power circuit 600 V UL Power circuit 690 V IEC 60947-4-1
Control circuit voltage limits0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 50 Hz 0.85...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 60 Hz 1...1.1 Uc (140...158 °F (60...70 °C)):operational AC 50/60 Hz
[Ue] rated operational voltagePower circuit Power circuit <= 300 V DC
[Uimp] rated impulse withstand voltage6 kV IEC 60947
[Icw] rated short-time withstand current640 A 104 °F (40 °C) - 10 s for power circuit 900 A 104 °F (40 °C) - 1 s for power circuit 110 A 104 °F (40 °C) - 10 min for power circuit 260 A 104 °F (40 °C) - 1 min for power circuit
Breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit

All specifications

LC1D65008M7 additional specifications
ParameterValue
[Ith] conventional free air thermal current80 A (at 140 °F (60 °C)) for power circuit
Inrush power in140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Power dissipation per pole9.6 W AC-1
Hold-in power consumption in13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Poles description4P
Pole contact composition2 NO + 2 NC
Utilisation categoryAC-1
IP degree of protectionIP20 front face IEC 60529
Mounting supportPlate Rail
Connections - terminalsControl circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: solid without cable end
Pollution degree3
Operating altitude0...9842.52 ft (0...3000 m)
Depth4.9 in (125 mm)
Width3.3 in (85 mm)
Height5 in (127 mm)
Electrical durability1.4 Mcycles 80 A AC-1 <= 440 V
Mechanical durability6 Mcycles
StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1
RangeTeSys
CategoryUS10I1222357
Operating time4...19 ms opening 12...26 ms closing
Coil technologyWithout built-in suppressor module
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation4...5 W at 50/60 Hz
Protective coverWith
Average impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
Device short nameLC1D
Tightening torqueControl circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04...0.05 in² (25...35 mm²) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002...0.04 in² (1...25 mm²) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Compatibility codeLC1D
Overvoltage categoryIII
Protective treatmentTHIEC 60068-2-30
Contactor applicationResistive load
Mechanical robustnessShocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz)
Associated fuse rating125 A gG at 125 A gG at <= 690 V coordination type 2 for power circuit
Maximum operating rate3600 cyc/h at 60 °C
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity1000 A at 440 V for power circuit conforming to IEC 60947
Permissible ambient air temperature around the device-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating

Product details

Integrator brief

The Schneider Electric LC1D65008M7 is a TeSys Deca 4-pole contactor rated for 80 A in AC-1 resistive duty, with electrical durability of 1.4 Mcycles at that load. Coil is AC 50/60 Hz without built-in suppressor; inrush is 140 VA at 60 Hz and 160 VA at 50 Hz. Heat dissipation runs 4–5 W at 50/60 Hz. Dimensions fit a 3.3 x 5 x 4.9 in envelope (85 x 127 x 125 mm), mounts on plate or rail. Front face IP20; pollution degree 3.

Panel wiring

Power circuit screw clamp terminals accept 1–35 mm² flexible without ferrule (torque 70.8 lbf·in) or 1–25 mm² with ferrule (torque 44.3 lbf·in). Use hexagonal 4 mm bit. Control circuit terminals take 1–4 mm² flexible without ferrule or 1–2.5 mm² with ferrule; torque to 15.05 lbf·in with Pozidriv #2. Associated fuse rating is 125 A gG at ≤690 V for type 2 coordination on power circuit.

Certified to UL 60947-4-1, CSA C22.2 No 14, IEC 60947-4-1, and EN 60947-4-1. Flame retardance V1 per UL 94; fire resistance 850 °C per IEC 60695-2-1. Protective treatment TH per IEC 60068-2-30; climatic withstand per IACS damp heat. Overvoltage category III, rated breaking capacity 1000 A at 440 V.

Sourcing

This part is specified by order code LC1D65008M7 – no cross-shipment from a lower current variant.

Frequently asked questions

What is the depth of the LC1D65008M7?

Depth is 4.9 in (125 mm).

What product range does the LC1D65008M7 belong to?

It is part of the TeSys Deca range.

What compliance certifications does the LC1D65008M7 carry?

Certified to UL 60947-4-1, CSA C22.2 No 14, IEC 60947-4-1, and EN 60947-4-1.

What coil type does the LC1D65008M7 use?

It uses an AC coil at 50/60 Hz without a built-in suppressor module.

What is the rated breaking capacity of the LC1D65008M7?

Rated breaking capacity is 1000 A at 440 V for the power circuit, conforming to IEC 60947.

MPN
LC1D65008M7