Skip to main content
Schneider Electric LC1E500BSCT1S260N

Schneider LC1E500BSCT1S260N Easy TeSys DC Contactor 500A 24V DC | aoctrl

MPN LC1E500BSCT1S260N
Active

Schneider Electric Easy Teys Control, 1-pole DC contactor, order code LC1E500BSCT1S260N, 1500 V DC switching, 500 A continuous, 24 V DC coil.

$68.87 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1E500BSCT1S260N specifications
ParameterValue
End connection typeInternal Thread
Control circuit typeDC
Main product or component typeContactor
Coil voltage24 V DC
Insulation voltage ui1500 V IEC 60947-4-1 power circuit
IP ratingIP60
Temp operating max85 °C
Temp operating min-40 °C
Depth4.09 in (104 mm)
Width2.8 in (70 mm)
Height4.2 in (107.9 mm)
Electrical life cycles1000 cycles at 750 V, 500 A on resistive load for only breaking, 0.6 s open, 5.4 s break 800 cycles at 1000 V, 500 A on resistive load for only breaking, 0.6 s open, 5.4 s break 500 cycles at 1500 V, 500 A on resistive load for only breaking, 0.6 s open, 5.4 s break
Mechanical life cycles300000 cycles
ApplicationResistive load
Operating time50 ms on closing 30 ms on opening
Operating temperature-40...185 °F (-40...85 °C) operation -40...185 °F (-40...85 °C) storage

Product details

What it is – a single-pole DC contactor for high-voltage resistive loads

The impedance is just 0.5 mOhm at Ith 500 A, and it's rated for 300,000 mechanical cycles. This is not your typical AC motor contactor – it's built for DC applications where high voltage and moderate current switching are needed, like battery banks, solar DC bus disconnects, or industrial DC load breakers. With a maximum switching voltage of 1500 V DC and insulation voltage of 1500 V, it's a solid choice for 1500 V DC rail systems.

Mounting & panel fit – vertical support, M8 power terminals

Dimensions: 4.09 in deep, 2.8 in wide, 4.2 in tall. It's designed for vertical mounting (support included). IP60 protection keeps out dust; not a sealed IP65, so keep it in a dry cabinet. Torque the power circuit to 70.8–88.5 lbf·in (8–10 N·m) using the supplied M8 nut, flat and spring washers. The control circuit comes with a 30 cm 2-wire supply, so it's ready to wire into a 24 V DC control bus. One normally-open auxiliary contact is built in – useful for feedback to a PLC or status lamp.

Electrical performance – where this part lives

Rated for 500 A continuous, but can handle short overloads: 750 A for 15 min, 900 A for 120 s, and 8000 A for 5 ms (no fire, no explosion). The minimum switching voltage is 8 V DC, minimum current 0.1 A, so it's suitable for both heavy and light loads. Electrical endurance under DC stress: 1000 cycles at 750 V DC and 500 A resistive breaking, 800 cycles at 1000 V DC and 500 A, 500 cycles at 1500 V DC and 500 A. Coil dropout occurs at 0.1–0.75 Uc. Operates at altitudes up to 4000 m without derating.

MPN
LC1E500BSCT1S260N