Skip to main content
Schneider Electric LC1F1000M7 — Contactors

Schneider TeSys F LC1F1000M7 Contactor, 1250 A AC-3, 220 V C

MPNLC1F1000M7
Obsolete

Schneider Electric TeSys F series, LC1F1000M7, 3-pole contactor, 1250 A AC-3 at ≤440 V, 220 V AC 40–400 Hz coil, plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F1000M7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC1F1000M7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 440 V AC 50/60 Hz
Utilisation categoryAC-1 AC-3
LC1F1000M7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F1000M7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F1000M7 — Approvals
ParameterValue
StandardsEN 60947-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1
LC1F1000M7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

The LC1F1000M7 is a TeSys F direct-on-line contactor rated 1250 A conventional free-air thermal current (Ith) at 40 °C and 1250 A rated operational current (Ie) in AC-3 duty at ≤440 V, 50/60 Hz. That AC-3 figure governs motor switching — it handles 560 kW at 380–400 V three-phase, 630 kW at 415 V, and 670 kW at 440 V. Short-time withstand current (Icw) is 10 kA for 10 s, 7.5 kA for 30 s, and 3 kA for 10 min at 40 °C — this defines the coordination window with upstream protective devices. The 220 V AC control coil (40–400 Hz) draws through screw-clamp terminals accepting 1–4 mm² flexible or solid wire. Plate-mounted, not DIN rail; the 438 mm width and 332 mm height demand panel layout planning.

Lifecycle and sourcing reality — EOL hot phase

This part is flagged EOL hot (end-of-life, active phase-out). The TeSys F series is being superseded by newer TeSys ranges. If you are stocking spares for an existing panel, buy the last-run quantity now; if designing new, evaluate the current TeSys replacement family.

Deployment and integration

Plate-mounted in a motor control centre or standalone enclosure. The 0.1 mΩ average impedance at 1250 A 50 Hz means about 156 W dissipation per pole in AC-1 — adequate ventilation or forced cooling needed in a closed panel. Operating altitude 3000 m without derating; ambient range -5 to 40 °C operating, -60 to 80 °C storage.

Frequently asked questions

What is the closest alternative to LC1F1000M7 in the TeSys family?

The evidence does not list a pin-compatible direct successor. For a new design, evaluate the current TeSys range (e.g., TeSys GV or TeSys Deca) for equivalent AC-3 current rating and coil voltage. The LC1F1000M7 remains the correct spare for existing TeSys F panels.

MPN
LC1F1000M7