Skip to main content
Schneider Electric LC1F1154E7 — Contactors

Schneider Electric LC1F1154E7 TeSys F Contactor, 200 A AC-1,

MPNLC1F1154E7
Obsolete

Schneider Electric TeSys F, LC1F1154E7, 4-pole contactor, 200 A AC-1 at ≤440 V, 48 V AC 40-400 Hz coil, plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F1154E7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F1154E7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F1154E7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F1154E7 — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F1154E7 — Approvals
ParameterValue
StandardsIEC 60947-4-1 EN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-1
LC1F1154E7 — Mechanical
ParameterValue
Width200.5 mm
Height162 mm
Depth171 mm

Product details

The LC1F1154E7 is a 4-pole (4 NO) TeSys F contactor from Schneider Electric, rated 200 A at ≤440 V in AC-1 utilisation category — that's the resistive-load rating, so it's sized for heater banks, lighting, or transformer primary switching, not motor starting. The 48 V AC 40-400 Hz coil draws 770 VA inrush and 8.1 VA hold-in; the drop-out range is 0.2 to 0.55 Uc, meaning it releases reliably between about 9.6 and 26.4 V. Plate-mount only — no DIN-rail adapter on this frame size. The rated breaking capacity of 920 A per IEC 60947-4-1 tells you it can interrupt fault currents up to that level, though the associated fuse recommendation is 125 A aM or 200 A gG at ≤440 V for short-circuit coordination.

Standards compliance includes IEC 60947-4-1, EN 60947-1, JIS C8201-4-1, and EN 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C; impulse withstand voltage is 8 kV. Protective treatment is TH (tropicalised) for humid environments.

Plate-mounted — the 200.5 mm width, 162 mm height, and 171 mm depth require a backplate or sub-panel, not a DIN rail. Power circuit connections accept bar (up to 20 x 3 mm busbar), ring lugs (1 cable up to 95 mm²), or bolted connection. Control circuit uses screw clamp terminals accepting 1 to 4 mm² solid or flexible. Tightening torque is 10 N·m on the power circuit and 1.2 N·m on the control circuit. IP2X on the front face with shrouds per IEC 60529 and VDE 0106. Altitude rating is 3000 m without derating. Overvoltage category III.

Frequently asked questions

What is the rated operational current of LC1F1154E7?

The LC1F1154E7 is rated 200 A at ≤440 V in AC-1 utilisation category (resistive load).

What coil voltage does LC1F1154E7 use?

The control circuit voltage is 48 V AC at 40-400 Hz, with an operational range of 0.85 to 1.1 Uc and a drop-out range of 0.2 to 0.55 Uc.

Where can I buy LC1F1154E7?

The LC1F1154E7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does LC1F1154E7 comply with?

It complies with IEC 60947-4-1, EN 60947-1, JIS C8201-4-1, and EN 60947-4-1.

MPN
LC1F1154E7