Skip to main content
Schneider Electric LC1F1700F7 — Contactors

Schneider Electric LC1F1700F7 TeSys F Contactor, 1700 A AC-1

MPNLC1F1700F7
Obsolete

Schneider Electric TeSys F, LC1F1700F7, 3-pole contactor, 1700 A AC-1, 110 V AC coil, plate mount, EOL phase.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F1700F7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F1700F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F1700F7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F1700F7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F1700F7 — Approvals
ParameterValue
StandardsEN 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F1700F7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

The Schneider Electric LC1F1700F7 is a 3-pole TeSys F contactor rated for 1700 A in AC-1 utilisation category (resistive load) at 40 °C, with a 110 V AC control coil operating at 40–400 Hz. This is a heavy-duty, plate-mounted contactor sized for large resistive heating banks, furnace control, or high-current distribution switching — not a motor-starting contactor (that would be an AC-3 rated device).

The 1700 A AC-1 rating governs continuous resistive current. The contactor dissipates 36 W total (200 W per pole in AC-1 duty), so panel ventilation or forced cooling may be needed if enclosed with other high-heat devices. For short-circuit coordination, the associated fuse is 1600 A gG at ≤ 440 V; the contactor itself can withstand 10,000 A for 10 seconds (Icw). The control coil draws 2200 VA inrush and 36 VA holding at 20 °C; the drop-out voltage is 0.3–0.5 Uc (33–55 V for a 110 V coil), so verify your control supply stays above 85% of Uc during dips. Operating time is 100–170 ms opening, 40–75 ms closing — not a fast-switching device, but adequate for resistive load cycling at up to 600 cycles per hour at 55 °C.

Standards & Approvals

The LC1F1700F7 carries certification to EN 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. The rated insulation voltage is 1000 V per IEC/UL 60947-4-1, with an impulse withstand voltage of 8 kV (overvoltage category III). The protective treatment is TH (tropicalized) for humid environments. These approvals mean the contactor is accepted in European, North American, and Japanese installations — no separate regional variant needed.

Frequently asked questions

How do I get current pricing and availability for LC1F1700F7?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront; the part is sourced through independent distribution channels.

What compliance documentation does LC1F1700F7 carry?

The LC1F1700F7 is certified to EN 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V (IEC/UL) with 8 kV impulse withstand. Protective treatment is TH (tropicalized).

What is the closest alternative to LC1F1700F7 in the TeSys F family?

No official successor order code is listed in the lifecycle record. A parametric substitute from the TeSys F range would need to match the 1700 A AC-1 rating, 110 V AC coil, 3-pole configuration, and plate-mount footprint — but mounting dimensions and thermal dissipation must be verified against your existing panel layout before substitution.

MPN
LC1F1700F7