Skip to main content
Schneider Electric LC1F1854F7 — Contactors

Schneider Electric LC1F1854F7 TeSys F Contactor, 275 A AC-1,

MPNLC1F1854F7
Obsolete

Schneider Electric TeSys F series, LC1F1854F7, 4-pole contactor, 275 A AC-1 rated operational current, 110 V AC 40-400 Hz control circuit voltage, plate mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F1854F7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F1854F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1F1854F7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F1854F7 — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F1854F7 — Approvals
ParameterValue
StandardsIEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1
LC1F1854F7 — Mechanical
ParameterValue
Width208.5 mm
Height174 mm
Depth181 mm

Product details

The LC1F1854F7: Rated 275 A at <= 440 V in AC-1 utilisation category, so this contactor is sized for resistive loads — heaters, furnaces, lighting banks — where the current waveform is sinusoidal and inrush is minimal. The 4 NO power pole configuration gives four independent normally-open switching paths. The 110 V AC 40-400 Hz control coil pulls in at 0.85 to 1.1 Uc and drops out between 0.2 and 0.55 Uc at 55 °C. Closing time is 35 ms, opening 130 ms at rated control voltage. Rated operational voltage goes up to 690 V AC 50/60 Hz, with an insulation voltage of 1000 V per IEC 60947-4-1. The rated impulse withstand voltage is 8 kV, overvoltage category III. For fault protection, the associated fuse rating is 200 A aM or 315 A gG at <= 440 V. Breaking capacity is 1480 A conforming to IEC 60947-4-1.

Plate-mounted, not DIN-rail — plan for a backplate or sub-panel with bolted connections. Dimensions: 174 mm height, 208.5 mm width, 181 mm depth. Power circuit termination accepts bar connections (25 x 3 mm busbar), ring lugs up to 150 mm², or bolted connections. Control circuit uses screw clamp terminals accepting 1 to 4 mm² flexible or solid wire, with or without ferrules. Tightening torque: 1.2 N·m for control, 18 N·m for power.

Thermal and Environmental

Heat dissipation is 8 to 9.8 W across the assembly, with per-pole dissipation of 12 W in AC-3 and 25 W in AC-1. Average impedance is 0.33 mOhm at Ith 275 A 50 Hz. The protective treatment is TH (tropicalised). IP2X front face with shrouds per IEC 60529.

Certified to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1. Maximum operating rate is 2400 cycles per hour at 55 °C.

Frequently asked questions

Where can I buy LC1F1854F7?

The LC1F1854F7 is sourced through independent surplus and broker channels. It is quoted to order against an RFQ; availability and current pricing are confirmed at quote time.

What is the rated operational current of LC1F1854F7?

The rated operational current (Ie) is 275 A at <= 440 V in AC-1 utilisation category, at < 40 °C.

What control voltage does LC1F1854F7 use?

The control circuit voltage (Uc) is 110 V AC, 40 to 400 Hz.

What standards does LC1F1854F7 comply with?

It complies with IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1.

MPN