Skip to main content
Schneider Electric LC1F2100M7 — Contactors

Schneider TeSys F LC1F2100M7 Contactor, 2100 A AC-1, 220 VAC

MPNLC1F2100M7
Obsolete

Schneider Electric TeSys F LC1F2100M7, 3-pole contactor, 2100 A AC-1 rated operational current, 220 VAC 40-400 Hz control circuit, plate mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F2100M7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F2100M7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F2100M7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F2100M7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F2100M7 — Approvals
ParameterValue
StandardsIEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F2100M7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

The Schneider Electric TeSys F LC1F2100M7 is a 3-pole contactor rated for 2100 A in AC-1 duty (resistive loads) at up to 40 °C ambient. That AC-1 rating — 2100 A conventional free-air thermal current — means it's sized for heavy resistive switching, like large heating banks or furnace loads, not motor starting. The control circuit runs on 220 VAC 40-400 Hz, with a pickup range of 0.85 to 1.1 times nominal and dropout at 0.3 to 0.5 times nominal at 55 °C.

The 2100 A AC-1 rating is the headline number, but pay attention to the breaking capacity: 3150 A per IEC 60947-4-1. That's the current it can safely interrupt under fault conditions. The short-time withstand current (Icw) is 10 kA for 10 seconds at 40 °C — useful for coordination studies if you're sizing upstream protection. Associated fuse recommendation is 2000 A gG at up to 440 V. Plate-mounted, dimensions 438 mm wide x 332 mm high x 238.6 mm deep — plan your enclosure layout accordingly. Heat dissipation is 36 W total, 200 W per pole in AC-1 duty, so ventilation matters in a sealed panel.

The LC1F2100M7 carries compliance with IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C, and 1000 V per UL 60947-4-1. Impulse withstand voltage is 8 kV, overvoltage category III. Protective treatment is TH (tropicalized).

Frequently asked questions

What are the key ratings of LC1F2100M7?

Rated operational current is 2100 A in AC-1 (resistive loads) at up to 40 °C. Control circuit voltage is 220 VAC 40-400 Hz. Breaking capacity is 3150 A per IEC 60947-4-1. Short-time withstand current is 10 kA for 10 seconds at 40 °C.

What compliance documentation does LC1F2100M7 carry?

The contactor complies with IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1.

MPN
LC1F2100M7