Skip to main content
Schneider Electric LC1F5004V7

Schneider Electric LC1F5004V7 TeSys F Contactor, 700 A AC-1,

MPN LC1F5004V7
Obsolete

Schneider Electric TeSys F contactor, LC1F5004V7, 4-pole, 700 A AC-1, 400 VAC 40-400 Hz coil, plate mount, end-of-life.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1F5004V7 key specifications
ParameterValue
Control circuit typeAC at 40...400 Hz
Main product or component typeContactor
Voltage<= 460 V DC
Coil voltage400 V AC 40...400 Hz
Insulation voltage ui1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Current700 A (at <40 °C) at <= 440 V AC AC-1
Breaking capacity4000 A conforming to IEC 60947-4-1
Utilization categoryAC-1
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max55 °C
Temp operating min-5 °C

All specifications

LC1F5004V7 additional specifications
ParameterValue
Storage temperature-60...80 °C
Depth232 mm
Width288 mm
Height238 mm
Mechanical life cycles10 Mcycles
ApplicationResistive load
Operating time40...65 ms closing 100...170 ms opening
Operating temperature-5...55 °C
Permissible ambient air temperature around the device-40...70 °C

Product details

Commissioning and Integration Notes

The Schneider Electric LC1F5004V7 is a TeSys F contactor with four normally open power poles, rated 700 A in AC-1 utilisation category for resistive loads at ≤ 440 V AC and ≤ 40 °C ambient. The 400 V AC control coil (40-400 Hz) draws 1100 VA inrush and 18 VA hold-in power; operational limits are 0.85 to 1.1 Uc, drop-out between 0.3 and 0.5 Uc. Closing time spans 40-65 ms, opening 100-170 ms, which matters for sequencing interlocks where the slower opening must be factored into safety circuit response. Mounting is plate-based (not DIN rail), with dimensions 288 mm wide × 238 mm high × 232 mm deep. Power circuit connections use bolted bars (up to 40 × 5 mm busbar) or ring lugs up to 240 mm²; control wiring uses screw clamp terminals accepting 1-4 mm² flexible or solid. Tightening torque is 35 N·m on the power circuit and 1.2 N·m on the control circuit — the power torque is substantial, so a calibrated torque wrench is expected during panel build.

The LC1F5004V7 is a 4-pole, 700 A AC-1 contactor with a 400 VAC coil. Any drop-in replacement must match the coil voltage, pole count, and mounting footprint.

The 700 A AC-1 rating is the headline — this contactor is sized for pure resistive loads (heater banks, lighting, power factor correction capacitor banks) where inrush is low. For motor or inductive loads (AC-3 or AC-4 duty), the rated operational current would be significantly lower; this part is not selected for motor starting without derating. For high-speed switching applications (e.g., resistance welding controls), verify the thermal dissipation: 18 W total, 88 W per pole in AC-1 duty. The associated fuse recommendation is 500 A aM or 800 A gG at ≤ 440 V — this is the short-circuit protection coordination the designer must follow to maintain the contactor's SCCR. The control circuit is AC only (40-400 Hz), not DC — a common mis-selection trap. The 400 V coil voltage is standard for European 400/690 V three-phase systems where the control transformer secondary is 400 V line-to-line. Overvoltage category III and rated insulation voltage of 1000 V (IEC) / 1500 V (VDE) make it suitable for fixed-installation distribution panels with transient overvoltages up to 8 kV impulse withstand.

Environmental and Compliance Profile

The contactor carries TH protective treatment for tropical/humid environments. Altitude derating starts above 3000 m without derating, covering most installations below that. Standards compliance includes IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1, and JIS C8201-4-1. These cover the contactor's design, testing, and performance for low-voltage switchgear and controlgear. The evidence does not list UL, CSA, RoHS, or REACH documentation explicitly; verification of those certifications should be requested at the time of RFQ if required for the target jurisdiction.

MPN
LC1F5004V7