Skip to main content
Schneider Electric LC1F500V7 — Contactors

Schneider TeSys F LC1F500V7 Contactor, 700 A AC-3, 250 kW

MPNLC1F500V7
Obsolete

Schneider Electric TeSys F series, LC1F500V7, 3-pole contactor, 700 A rated operational current (AC-3), 250 kW motor power at 400 V AC, coil 400 V AC, plate mount, depth 232 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F500V7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC1F500V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1 AC-3 AC-4
LC1F500V7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F500V7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F500V7 — Approvals
ParameterValue
StandardsIEC 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1
LC1F500V7 — Mechanical
ParameterValue
Width233 mm
Height238 mm
Depth232 mm

Product details

The LC1F500V7: This part is in end-of-life (EOL) phase-out per the manufacturer. No direct successor is listed.

Motor power rating hits 250 kW at 380–400 V AC and 280 kW at 415 V — the key figure for sizing to a pump, fan, or compressor. Mechanical durability is 10 Mcycles, reflecting a heavy-duty switching cycle. The 18 W heat dissipation at rated load means panel ventilation should account for that thermal load.

Deployment and integration

Plate-mount design (not DIN rail) — plan for bolting to a backplate in the enclosure. Dimensions 238 mm high × 233 mm wide × 232 mm deep. Power connections are bar or lug terminals; control wiring uses screw clamps accepting 1–4 mm².

Certified to IEC 60947-4-1 and EN 60947-4-1. Also carries JIS C8201-4-1. Overvoltage category III.

Frequently asked questions

What is the closest pin-compatible alternative to LC1F500V7?

No direct pin-compatible replacement is listed by the manufacturer. For a parametric match, a contactor with a similar AC-3 rating (700 A) and coil voltage (400 V AC) from the same TeSys F family would be the closest functional alternative, but verify physical fit and wiring.

What is LC1F500V7's listed depth (232 mm) on this component line?

The depth is 232 mm. Overall dimensions: 238 mm high × 233 mm wide × 232 mm deep. Plate-mount only.

MPN
LC1F500V7