Specifications

LC1F6304V7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F6304V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F6304V7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F6304V7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F6304V7 — Approvals
ParameterValue
StandardsIEC 60947-1 EN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1
LC1F6304V7 — Mechanical
ParameterValue
Width389 mm
Height304 mm
Depth255 mm

Product details

The Schneider Electric LC1F6304V7 is a TeSys F 4-pole contactor rated for 1000 A in AC-1 duty (resistive load) at ≤440 V, with a 400 V AC 40–400 Hz coil. The four normally-open power poles handle switching for large resistive banks — think industrial ovens, furnace elements, or large lighting loads — where the current stays sinusoidal and inrush is modest. Plate-mounted, not DIN-rail; at 389 mm wide and 304 mm tall, it needs a backplate or sub-panel, not a standard enclosure rail.

The 1000 A AC-1 rating is the headline number, but note it applies at ≤40 °C ambient and ≤440 V. That 1000 A is the conventional free-air thermal current (Ith) at 50 Hz, with an average pole impedance of 0.12 mOhm — so each pole dissipates about 120 W at full load, and the whole contactor sheds 20 W total heat into the panel. That heat has to go somewhere; plan for ventilation or forced air if the enclosure is tight. The 4 NO pole configuration means all four poles switch together; there is no built-in auxiliary contact block. If you need N/C feedback or a status signal to a PLC, you'll add a separate auxiliary contact block (TeSys F series) on the side. The control circuit is screw-clamp terminals accepting 1–4 mm² flexible or solid wire, torqued to 1.2 N·m; the power circuit uses bolted busbar connections (60 x 5 mm bar) at 58 N·m — that's a substantial torque, so a calibrated torque wrench is expected. That's about one operation every 3 seconds — fine for cyclic resistive loads but not for high-speed motor reversing. The contactor is built to IEC 60947-4-1 and EN 60947-4-1, with a rated impulse withstand voltage of 8 kV and overvoltage category III, so it's suitable for fixed-installation industrial distribution panels. Altitude rating is 3000 m without derating — useful for high-altitude plants or mining sites. The front face carries IP20 protection with shrouds (per IEC 60529 and VDE 0106), meaning finger-safe from the front but not sealed against dust or moisture ingress elsewhere.

The contactor carries IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1 standards compliance. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. The protective treatment is TH (tropicalized humidity resistance). For RoHS, REACH, and UL documentation, the manufacturer's declaration package is available on request — we can provide the compliance certificate or declaration of conformity that matches the nameplate to your PO traceability requirements.

Frequently asked questions

Where can I buy the LC1F6304V7 and get a price?

We source the LC1F6304V7 through our independent distribution network of verified surplus and new-old-stock inventory. Submit an RFQ for current availability and pricing — we confirm condition (new-in-box, sealed, or pulled stock) and lead time at quote time.

What is the closest alternative to the LC1F6304V7 in the TeSys F family?

Within the TeSys F range, the closest functional equivalent would be another 4-pole, 1000 A AC-1 contactor with a 400 V AC coil. Since the LC1F6304V7 is end-of-life with no official successor listed, a parametric search across the TeSys F catalog for the same pole count, coil voltage, and AC-1 current rating is the practical path. Contact us with your application details and we can help identify a suitable cross-reference.

What is the depth of the LC1F6304V7?

The LC1F6304V7 has a depth of 255 mm, with a width of 389 mm and height of 304 mm. It is plate-mounted, not DIN-rail, so plan for backplate or sub-panel installation.

What compliance documentation does Schneider provide for the LC1F6304V7?

The LC1F6304V7 complies with IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1 standards. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Protective treatment is TH (tropicalized). RoHS, REACH, and UL documentation is available on request as part of the manufacturer's declaration package.

MPN