Skip to main content
Schneider Electric LC1K06013FE7 — Contactors

Schneider TeSys K LC1K06013FE7 Contactor, 3P, 6A AC-3, 115V

MPNLC1K06013FE7
Active

Schneider Electric TeSys K contactor, 3P, AC-3/AC-3e 6 A at ≤440 V, 1 NC auxiliary, 115 V AC coil, spring terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1K06013FE7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control
LC1K06013FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-4
LC1K06013FE7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K06013FE7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K06013FE7 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
LC1K06013FE7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LC1K06013FE7 is a TeSys K three-pole contactor rated for motor control in AC-3 and AC-3e duty at 6 A up to 440 V, with a 115 V AC coil. It carries one normally closed instantaneous auxiliary contact. Coil inrush is 30 VA at 20 °C, holding at 4.5 VA; heat dissipation runs 1.3 W. The coil has no built-in suppressor module, so if you are driving it from a PLC output or solid-state relay, plan an external flyback diode or RC snubber across the coil to protect the switching device.

Electrical durability is 1.3 million cycles at 6 A AC-3, and 50,000 cycles at 36 A AC-4 — the AC-4 figure matters if you are jogging or inching the motor under load, which wears the contacts faster. Mechanical durability is 10 million cycles, so the mechanical life is rarely the constraint in a control panel. Minimum switching capability is 5 mA at 17 V for signalling circuits — useful if the auxiliary contact feeds a low-power PLC input or indicator, but verify the load is above that threshold to avoid contact film issues. The contactor is rated for safety-related applications with a B10d of 1,369,863 cycles at nominal load per EN/ISO 13849-1. That is a statistical reliability figure for the dangerous failure rate — useful if you are calculating the PFHd for a safety circuit. Operating time is 10 to 20 ms for both coil energisation and de-energisation, with a non-overlap distance of 0.5 mm between NO and NC poles — fast enough for most sequencing but not a high-speed transfer switch. Maximum operating rate is 3600 cycles per hour, or one operation per second — fine for frequent cycling in packaging or material handling.

Certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1 — covers most global markets without a separate variant. Also listed to IEC 60335-1 and UL 60335-2-40 for appliance applications. Shock and vibration ratings are given per IEC 60068-2-27 and -2-6 — the contactor stays closed under 10 Gn on X and 15 Gn on Y/Z axes, which is robust for mobile or rail equipment.

Frequently asked questions

What are the key ratings for this contactor?

It is a 3-pole contactor rated 6 A in AC-3/AC-3e duty at ≤440 V, with a 115 V AC coil. It has one normally closed auxiliary contact, spring terminals, and measures 45 x 58 x 57 mm. Electrical durability is 1.3 million cycles at 6 A AC-3.

What compliance documentation does this brand provide for the LC1K06013FE7?

The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. It also meets IEC 60335-1 and UL 60335-2-40 for appliance use. Flame retardance is V1 per UL 94.

What is the closest alternative to the LC1K06013FE7 in the TeSys K family?

Within the TeSys K range, the closest alternative would be a variant with a different coil voltage (e.g., 24 V AC or 230 V AC) or a different auxiliary contact configuration. The core 6 A AC-3 rating and 3-pole frame are shared across the LC1K06xxx series. For a direct pin-compatible swap, match the coil voltage and auxiliary contact count.

MPN
LC1K06013FE7