Schneider Electric LC1K06106L7 — Contactors

TeSys K LC1K06106L7 Contactor, 3P, 6A AC-3, 200-208V Coil

MPNLC1K06106L7
Obsolete

Schneider Electric TeSys K series, LC1K06106L7, 3-pole contactor, AC-3/AC-3e 6A at 440V, 200-208V AC standard coil, 1 NO auxiliary contact.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1K06106L7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control
LC1K06106L7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-4
LC1K06106L7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K06106L7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K06106L7 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
LC1K06106L7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K06106L7 is a TeSys K series 3-pole contactor rated for motor control in AC-3 and AC-3e utilisation categories at 6 A up to 440 V, with an additional AC-4 rating for inching/jogging duty. The coil is a 200-208 V AC standard type without a built-in suppressor module, so you will need to add an RC snubber or varistor across the coil if driving it from a PLC output or solid-state relay. It carries a single normally-open instantaneous auxiliary contact (1 NO) for feedback or interlocking. The contactor is rated for 10 million mechanical cycles and 1.3 million electrical cycles at the AC-3 rating, with a maximum operating rate of 3600 cycles per hour.

The physical footprint (57 mm depth, 45 mm width, 58 mm height) and ring-lug terminal style are consistent across the K-frame contactors.

The AC-3 rating of 6 A at 440 V governs motor switching — this contactor is sized for small three-phase motors up to roughly 2.2 kW at 400 V. The AC-4 rating drops to 36 A but only for 50,000 cycles, reflecting the severe duty of plugging or inching. If your application requires frequent reversing or jogging, factor that reduced electrical life into your maintenance schedule. The coil draws 30 VA inrush and 4.5 VA holding at 20 °C, dissipating 1.3 W. The control circuit operates from 0.8 to 1.15 times the rated coil voltage and drops out at 0.2 times Uc below 50 °C. Minimum switching capability is 5 mA at 17 V for the signalling circuit, so it can interface with low-level PLC inputs without issues. Standards compliance includes EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1, plus IEC 60335-1 and UL 60335-2-40 for appliance applications. The IP2X finger protection rating (VDE 0106) means it is safe for open-panel mounting but not for washdown environments.

Frequently asked questions

What replaces the LC1K06106L7?

The direct successor within the TeSys K family is the LC1K0610x7 series with the same 200-208 V AC coil voltage. Verify the auxiliary contact configuration (1 NO) matches your requirement before ordering.

What are the key ratings for this contactor?

It is a 3-pole contactor rated 6 A in AC-3 at 440 V for motor control, with a 200-208 V AC coil. It includes one normally-open auxiliary contact and is rated for 10 million mechanical cycles.

What compliance certifications does it carry?

It complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, IEC 60335-1, and UL 60335-2-40. It also meets NF F 16-101 for railway fire safety.

MPN
LC1K06106L7