Skip to main content
Schneider Electric LC1K0901B5 — Contactors

Schneider Electric LC1K0901B5 TeSys K Contactor, 9A AC-3, 24

MPNLC1K0901B5
Active

Schneider Electric TeSys K LC1K0901B5, 3-pole contactor, 9 A AC-3/AC-3e, ≤440 V, 1 NC auxiliary contact, 24 V 50 Hz coil, screw clamp terminals.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K0901B5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load Motor control

Ratings & Performance

LC1K0901B5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-1 AC-4

Contacts & Poles

LC1K0901B5 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K0901B5 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Approvals

LC1K0901B5 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ

Mechanical

LC1K0901B5 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K0901B5 is a TeSys K series 3-pole contactor rated for motor control at 9 A in AC-3 and AC-3e duty up to 440 V, with a 24 V 50 Hz coil and one normally-closed auxiliary contact. It carries global approvals including EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1, so it fits panels destined for North America, Europe, or Asia without requalification.

AC-3e extends that to energy-efficient motors with higher inrush. Electrical durability at 9 A AC-3 is 1.3 million cycles, which covers most conveyor and pump duty cycles for years. For resistive loads (AC-1) it handles 20 A, and for plugging/inching (AC-4) it is rated 54 A but with only 20,000 cycles — so use AC-4 sparingly, not for continuous jogging. The coil draws 30 VA inrush and 4.5 VA hold-in at 20 °C, dissipating 1.3 W. That heat is low enough to pack multiple contactors on a DIN rail without forced cooling. The control voltage limits are 0.8...1.15 Uc operational, with dropout at ≥0.20 Uc below 50 °C — so it stays pulled in through brownouts down to about 19 V. The single NC auxiliary contact is instantaneous, rated for signalling down to 5 mA and 17 V minimum switching — enough for PLC digital inputs but not for dry-contact logic at lower levels.

Mounts on plate or rail; screw-clamp terminals accept 1.5...4 mm² solid or 0.34...2.5 mm² flexible with ferrule, torqued to 0.8...1.3 N·m. IP20 finger-safe per VDE 0106, so it can sit in an open panel behind a locked door.

Frequently asked questions

What are the key global standards this contactor meets?

It complies with EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and GB/T 14048.4, plus IEC 60335-1 Clause 30.2 for appliance applications.

What is the depth of the LC1K0901B5?

The depth is 57 mm, with a width of 45 mm and height of 58 mm.

What is the closest alternative to this contactor in the TeSys K family?

Within the same TeSys K series, the LC1K0901B7 uses a 24 V 60 Hz coil instead of 50 Hz; the LC1K0901B5 is the 50 Hz variant. For a different coil voltage, the LC1K0901P7 (230 V 60 Hz) or LC1K0901M7 (220 V 50 Hz) are direct frame-and-rating matches.

MPN
LC1K0901B5