Skip to main content
Schneider Electric LC1K0910B5 — Contactors

Schneider Electric LC1K0910B5 TeSys K Contactor, 9A AC-3, 24

MPNLC1K0910B5
Obsolete

Schneider Electric TeSys K contactor, 3P, 9A AC-3/AC-3e, 24V 50Hz coil, 1NO auxiliary contact, screw clamp terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1K0910B5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC1K0910B5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-1 AC-4
LC1K0910B5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1K0910B5 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC1K0910B5 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
LC1K0910B5 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K0910B5 is a TeSys K series contactor with 3 power poles (3 NO), rated 9 A in AC-3 and AC-3e utilization categories at up to 440 V. The coil is 24 V at 50 Hz, drawing 30 VA inrush and 4.5 VA hold-in power at 20 °C. A single instantaneous 1 NO auxiliary contact is built in.

The 9 A AC-3 rating is the motor-switching current — it handles a 3-phase induction motor load up to about 4 kW at 400 V. The AC-3e rating adds a bit of margin for energy-efficient motors with higher inrush. Electrical durability is 1.3 million cycles at that 9 A AC-3 load, which is solid for a compact frame. The 20 A AC-1 rating (resistive load) gives headroom for heater or lighting circuits, but the mechanical life of 10 million cycles is what governs in low-load switching. Heat dissipation is 1.3 W — negligible in a ventilated enclosure, but worth noting if you're packing several contactors in a sealed panel. The IP20 finger-safe terminals (per VDE 0106) are standard for control cabinet use; no washdown rating here.

Screw clamp terminals accept 1.5–4 mm² solid or 0.34–2.5 mm² flexible with ferrule. Tightening torque is 0.8–1.3 N·m. Coil de-energisation and NO opening take 10–20 ms; coil energisation and NO closing are the same range. Minimum switching capability is 5 mA at 17 V for signalling circuits — fine for PLC inputs but not for dry-contact logic below those thresholds.

Frequently asked questions

What are the key ratings of the LC1K0910B5?

It is a 3-pole contactor rated 9 A in AC-3/AC-3e at up to 440 V, with a 24 V 50 Hz coil drawing 30 VA inrush and 4.5 VA hold-in. It has one NO auxiliary contact and screw clamp terminals.

What compliance certifications does the LC1K0910B5 carry?

It is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and meets IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ. Flame retardance is V1 per UL 94.

MPN
LC1K0910B5