Skip to main content
Schneider Electric LC1K1610D7 — Contactors

Schneider LC1K1610D7 TeSys K Contactor, 3P, 16A AC-3, 42V Co

MPNLC1K1610D7
Active

Schneider Electric TeSys K contactor, LC1K1610D7, 3-pole, AC-3/AC-3e 16 A ≤440 V, 1 NO aux, 42 V AC coil.

$63.50Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K1610D7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC1K1610D7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e

Contacts & Poles

LC1K1610D7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K1610D7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94

Approvals

LC1K1610D7 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ

Mechanical

LC1K1610D7 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC1K1610D7 is a TeSys K 3-pole contactor rated for AC-3 and AC-3e duty at 16 A up to 440 V, with a 42 V AC coil and one normally open auxiliary contact. It's built for switching motor loads — think conveyors, pumps, fans — inside a control panel, and it carries approvals across EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1, so it's accepted in most industrial jurisdictions without extra paperwork.

The AC-3 rating at 16 A is the number that matters for motor switching — it tells you the contactor handles inrush during start and breaks full-load current under normal running. The 42 V AC coil is common in older or low-voltage control circuits; the pickup range is 0.8 to 1.15 Uc (so about 33.6 to 48.3 V), and it drops out at 0.2 Uc (8.4 V) below 50 °C. Heat dissipation is 1.3 W steady-state, which is modest enough that you don't need to derate adjacent components in a typical DIN-rail layout.

Screw-clamp terminals accept 1.5 to 4 mm² solid or 0.34 to 2.5 mm² flexible with ferrule; torque to 0.8–1.3 N·m. The single NO auxiliary contact is instantaneous, so it's fine for a status feedback or interlock, but if you need more than one aux you'll add a side-mount block.

This is a current-production part.

Frequently asked questions

What compliance documentation does this brand provide for the LC1K1610D7?

The contactor carries certifications to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1, plus IEC 60335-1 Clause 30.2 and UL 60335-2-40 Annex JJ for appliance applications. RoHS and REACH declarations are standard from Schneider for this series.

What are the key dimensions for panel layout?

Width is 45 mm, height 58 mm, depth 57 mm — fits a standard 45 mm DIN-rail slot with room for side-mount aux blocks.

MPN
LC1K1610D7