Skip to main content
Schneider Electric LC1K1610P5 — Contactors

Schneider TeSys K LC1K1610P5 Contactor, 16A AC-3, 230V 50Hz

MPNLC1K1610P5
Obsolete

Schneider Electric TeSys K contactor, LC1K1610P5, 3-pole, 16 A AC-3/AC-3e ≤440 V, 1 NO auxiliary contact, 230 V 50 Hz coil, screw clamp terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1K1610P5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC1K1610P5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e

Contacts & Poles

LC1K1610P5 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1K1610P5 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94

Approvals

LC1K1610P5 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ

Mechanical

LC1K1610P5 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric TeSys K LC1K1610P5 is a 3-pole contactor rated for motor control in AC-3 and AC-3e utilisation categories up to 440 V, switching 16 A. The 230 V 50 Hz coil draws 30 VA inrush and 4.5 VA hold-in power, dissipating 1.3 W — a light thermal load inside a crowded panel. Electrical durability is 1.3 million cycles at 16 A AC-3/AC-3e, backed by 10 million mechanical cycles, so this contactor is sized for frequent switching on conveyor or pump duty without premature wear.

The LC1K1610P5 carries EN/IEC 60947-4-1 (the main contactor standard for motor starting and switching), UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. It also meets IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ for heat-rise limits in household and HVAC appliances. This means the part is accepted in panels destined for North America, Europe, Japan, and appliance applications without a separate certification step. Flame retardance is V1 per UL 94, and the IP20 finger-safe protection (VDE 0106) suits it for open-panel mounting inside an enclosure.

Mounts on plate or DIN rail — the 45 mm width and 58 mm height fit standard TeSys K backplate layouts. Screw-clamp terminals accept 1.5 to 4 mm² solid or 0.75 to 4 mm² flexible cable, with a tightening torque of 0.8 to 1.3 N·m. The single NO auxiliary contact is built in, so no add-on block is needed for basic feedback. Altitude derating starts above 2000 m. The contactor is rated for 3600 cycles per hour maximum operating rate.

Frequently asked questions

What compliance documentation does this brand provide for LC1K1610P5?

The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. It also meets IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ for appliance applications. Flame retardance is V1 per UL 94.

What is LC1K1610P5's listed depth on this component line?

The depth is 57 mm, with a width of 45 mm and height of 58 mm — a compact footprint for DIN-rail or plate mounting.

What is LC1K1610P5's listed range on this component line?

It belongs to the Schneider Electric TeSys K range of contactors, designed for motor control and general switching up to 16 A AC-3.

MPN
LC1K1610P5