Specifications

LC2D115004M5 — Identification
ParameterValue
Product / component typeChangeover contactor
Series / rangeTeSys
ApplicationResistive load
LC2D115004M5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Power circuit: <= 460 V DC
Utilisation categoryAC-1 AC-3 AC-3e AC-4
LC2D115004M5 — Contacts & Poles
ParameterValue
Pole configuration4P
LC2D115004M5 — Environmental
ParameterValue
IP degree of protectionIP20 front face conforming to IEC 60529
Operating altitude0...3000 m
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 6 Gn for 11 ms
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
LC2D115004M5 — Approvals
ParameterValue
StandardsCSA C22.2 No 60947-4-1 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.4
LC2D115004M5 — Mechanical
ParameterValue
Width334 mm
Height158 mm
Depth148 mm

Product details

Overview

The LC2D115004M5 is a Schneider TeSys Deca Advanced reversing contactor rated for 200 A switching current across 4 poles, with a 220 V AC 50 Hz control coil. It ships preassembled with the reversing power busbar, cutting panel build time for motor reversing applications. Rated for utilization categories AC-1, AC-3, AC-3e, and AC-4, it carries UL, CSA, and IEC certifications for global acceptance.

The 200 A switching current and 4-pole configuration suit resistive and motor loads up to the AC-3 rating. The preassembled reversing busbar eliminates separate wiring for forward/reverse interlocking, reducing panel space and commissioning time.

MPN
LC2D115004M5