Skip to main content
Schneider Electric LC2K06013FE7 — Contactors

TeSys K LC2K06013FE7 Reversing Contactor, 3P, 6A AC-3, 115V

MPNLC2K06013FE7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 6 A, 1 NC, 115 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K06013FE7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K06013FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K06013FE7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K06013FE7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K06013FE7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The unit ships preassembled with the reversing power busbar, saving panel wiring time on motor-reversing circuits.

The AC-3 rating of 6 A at <=440 V governs motor switching: it handles a 3-phase induction motor drawing up to 6 A in the full-load starting and running regime. The 115 V AC coil is a standard control voltage in North American and some European panels; verify the control transformer taps before wiring.

The contactor withstands shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: up to 15 Gn on Y and Z axes when closed, 10 Gn on X. Vibration resistance is 4 Gn closed, 2 Gn open across 5–300 Hz. Operating altitude is 2000 m without derating. Flame retardance meets UL 94 V1 and NF F 16-101/102 requirements.

The preassembled reversing busbar eliminates one wiring step and reduces the chance of phase-crossing errors. Mounts on standard DIN rail. The 1 NC auxiliary contact is typically wired into the safety circuit or as an interlock in the reversing logic.

Frequently asked questions

What are the key ratings for this contactor?

It is a 3-pole reversing contactor rated AC-3 at 6 A up to 440 V, with a 115 V AC coil and one normally closed auxiliary contact. It also carries an AC-4 utilisation category for reversing and inching duty.

What is the physical size of this part?

The LC2K06013FE7 measures 90 mm wide, 58 mm high, and 57 mm deep.

What compliance certifications does it carry?

It has IP20 finger-safe protection per VDE 0106, flame retardance to UL 94 V1 and NF F 16-101/102, and protective treatment conforming to IEC 60068 and DIN 50016.

MPN
LC2K06013FE7