Skip to main content
Schneider Electric LC2K09103P7 — Contactors

TeSys K LC2K09103P7 Reversing Contactor, 9 A AC-3, 230 VAC C

MPNLC2K09103P7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 9 A, 1 NO, 230 V AC coil, IP20, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K09103P7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationResistive load Motor control
LC2K09103P7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-1
LC2K09103P7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K09103P7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K09103P7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated for AC-3 duty at 9 A up to 440 V and AC-1 resistive loads, it uses a 230 V AC coil. The IP20 finger-safe enclosure (VDE 0106) suits panel-mount installations where the contactor is behind a cabinet door.

The preassembled reversing busbar means the mechanical interlock and power wiring between the two contactor halves is factory-fitted; only the coil control wires and motor/power connections need termination in the field. Operating altitude is 2000 m without derating; above that, the dielectric strength and thermal dissipation must be recalculated per IEC 60947.

Frequently asked questions

What is the closest alternative to the LC2K09103P7?

The official manufacturer replacement order code is not recorded in this listing. The closest form-fit-function equivalent would be a TeSys K or TeSys Deca reversing contactor with the same pole count (3P), coil voltage (230 V AC), and AC-3 current rating (9 A at ≤440 V). Check the mounting footprint and busbar arrangement — the preassembled reversing busbar on this part may require an accessory kit on a newer series.

What compliance documentation is available for this part?

The part carries V1 flame retardance per UL 94 and compliance with NF F 16-101 and NF F 16-102 (French railway fire/smoke standards). IP20 per VDE 0106. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6. No RoHS or REACH statement is present in this record.

MPN