Rated AC-3 at 12 A up to 440 V, it handles the forward/reverse switching of a small three-phase motor, such as a conveyor drive or pump. The coil is 220-230 V AC, and the contactor carries one normally closed auxiliary contact (1 NC). The 57 mm depth, 90 mm width, and 58 mm height fit the standard DIN-rail footprint of the TeSys K range, so it slots into a control panel alongside other IEC modular gear.
Schneider TeSys K LC2K12017M7 Reversing Contactor, 12A AC-3,
Schneider Electric TeSys K reversing contactor, LC2K12017M7, 3P, AC-3 12A ≤440 V, 1 NC, 220-230 V AC coil, preassembled with reversing power busbar.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Reversing contactor |
| Series / range | TeSys |
| Application | Motor control Resistive load |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit |
| Utilisation category | AC-1 AC-4 AC-3 |
| Parameter | Value |
|---|---|
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to VDE 0106 |
| Operating altitude | 2000 m without derating |
| Mechanical robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Protective treatment / pollution degree | TC conforming to IEC 60068 TC conforming to DIN 50016 |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Parameter | Value |
|---|---|
| Width | 90 mm |
| Height | 58 mm |
| Depth | 57 mm |
Product details
Frequently asked questions
What are the key ratings I need to check for fit?
The critical ratings are AC-3 motor-switching current of 12 A at ≤440 V, coil voltage of 220-230 V AC, 3-pole configuration with 3 NO main contacts and 1 NC auxiliary, and the preassembled reversing busbar. Dimensions are 57 mm deep, 90 mm wide, and 58 mm high.
What compliance documentation is available for this part?
The contactor carries V1 flame retardance per UL 94, and meets NF F 16-101 and NF F 16-102 for fire safety in rail applications. IP20 protection is per VDE 0106. Protective treatment complies with IEC 60068 and DIN 50016. Mechanical robustness is rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6.