LC2K16105C72 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16105C72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LC2K16105C72 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16105C72 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16105C72 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K16105C72 is a TeSys K reversing contactor — a 3-pole device rated AC-3 at 16 A up to 440 V, with a 36 V AC coil and one normally-open auxiliary contact. It ships preassembled with the reversing power busbar, which saves panel builders the wiring step of linking two contactors for forward/reverse motor control. Rated operational voltage on the power circuit is 690 V AC at 50/60 Hz, so it handles 400 V and 480 V line supplies without derating. The AC-3 category means it switches squirrel-cage motors during starting and running; AC-4 covers plugging and inching duty, which is the harder thermal cycle.

IP20 finger-safe protection means it can sit in a control cabinet without additional shrouding on the front face. Altitude derating kicks in above 2000 m — no reduction needed for most industrial sites.

No broker channel or surplus hunt needed.

Flame retardance meets V1 per UL 94 and also satisfies NF F 16-101 and NF F 16-102 Requirement 2 — the French rail standard for fire behavior. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance in humid or mildly aggressive atmospheres. Mechanical robustness is specified: the contactor withstands 10 Gn shocks on Y and Z axes (15 Gn on X) for 11 ms when closed, and 6–10 Gn when open. Vibration resistance is 4 Gn closed, 2 Gn open across 5–300 Hz per IEC 60068-2-6.

Frequently asked questions

What are the key ratings for this reversing contactor?

It is a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 36 V AC coil and one NO auxiliary contact. The power circuit is rated for 690 V AC at 50/60 Hz. It ships preassembled with the reversing power busbar.

What compliance documentation is available for this part?

Flame retardance is V1 per UL 94 and meets NF F 16-101/102 Requirement 2 for rail applications. Protective treatment conforms to IEC 60068 and DIN 50016. Shock and vibration testing follows IEC 60068-2-27 and IEC 60068-2-6.

What are the mounting dimensions?

Width is 90 mm, height 58 mm, depth 57 mm. IP20 finger-safe protection allows installation in standard enclosures without additional front-face shrouding.

MPN
LC2K16105C72