Schneider Electric LC2K16105F7 — Contactors

TeSys K LC2K16105F7 Reversing Contactor, 3P, 16A AC-3, 110VA

MPNLC2K16105F7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 110 V AC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K16105F7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16105F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K16105F7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16105F7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16105F7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Three poles, normally open, rated for AC-3 and AC-4 duty at 16 A up to 440 V, with a 110 V AC coil. IP20 finger-safe enclosure per VDE 0106, so it's panel-mount only — no washdown exposure.

The AC-3 rating at 16 A up to 440 V covers starting and stopping a squirrel-cage induction motor under load. The AC-4 rating covers plugging and inching at full locked-rotor current. Mechanical shock and vibration ratings are specified per IEC 60068-2-27 and IEC 60068-2-6: the contactor holds closed through 10 Gn on Y and Z axes and 4 Gn vibration at 5–300 Hz. That is enough for most industrial panels on a machine base, but not for direct engine-mount or high-shock applications like stamping presses. Altitude derating kicks in above 2000 m — no derating needed below that, so it is fine for most plant-floor installations.

Frequently asked questions

What are the key ratings for the LC2K16105F7?

It is a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 110 V AC coil. IP20 protection, operating temperature range -25 to 50 °C, and altitude limit of 2000 m without derating.

What compliance documentation is available for the LC2K16105F7?

The contactor carries a V1 flame retardance rating per UL 94 and meets NF F 16-101 and NF F 16-102 requirements. Protective treatment conforms to IEC 60068 and DIN 50016. Specific RoHS/REACH declarations would be part of the documentation package available upon request.

MPN