Skip to main content
Schneider Electric LC2K16105R7 — Contactors

Schneider TeSys K LC2K16105R7 Reversing Contactor, 3P, 16 A

MPNLC2K16105R7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 440 V AC coil, IP20, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K16105R7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16105R7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LC2K16105R7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16105R7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16105R7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated AC-3 ≤440 V 16 A, it handles reversing duty on a motor load up to that current; AC-3 is the motor-switching category per IEC 60947-4-1, so the 16 A figure is the real-world current for starting and stopping a squirrel-cage induction motor, not a resistive-heater rating. The coil is 440 V AC, matching a common control voltage in European 400 V three-phase panels. Operating temperature spans -25 to 50 °C, with storage from -50 to 80 °C; the 2000 m altitude rating without derating covers most industrial sites below that elevation.

This reversing contactor is sized for a control panel — the 90 mm width, 58 mm height, and 57 mm depth fit a standard DIN-rail footprint alongside other TeSys K components. The preassembled reversing busbar saves panel-build time: no separate interlock wiring, just land the motor leads and control coil. Mechanical robustness is specified for shock and vibration — 10 Gn on Y and Z axes with contactor closed, 4 Gn vibration closed at 5–300 Hz — so it holds in on mobile equipment or near rotating machinery. Flame retardance meets V1 per UL 94 and Requirement 2 per NF F 16-101/102, which matters for rail and transit applications where fire-smoke-toxicity compliance is mandatory. The protective treatment conforms to IEC 60068 and DIN 50016, covering corrosion resistance in humid or mildly aggressive atmospheres.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 motor-switching rating is 16 A at ≤440 V. The coil is 440 V AC. It is a 3-pole (3 NO) reversing contactor with IP20 finger protection. Operating temperature range is -25 to 50 °C.

What compliance documentation does this part carry?

Flame retardance is V1 per UL 94 and Requirement 2 per NF F 16-101/102. Protective treatment conforms to IEC 60068 and DIN 50016. IP20 per VDE 0106. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6.

What is the physical size of the LC2K16105R7?

Width 90 mm, height 58 mm, depth 57 mm. DIN-rail mountable.

MPN
LC2K16105R7