Schneider TeSys K LC2K1610P72 Reversing Contactor, 16 A, 230

MPNLC2K1610P72
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NO, 230 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K1610P72 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K1610P72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K1610P72 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1610P72 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1610P72 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric TeSys K LC2K1610P72 is a reversing contactor, 3-pole, rated for AC-3 and AC-4 utilisation categories.

The 230 V AC coil is standard for European control circuits; verify your control transformer voltage matches. IP20 protection (VDE 0106) means finger-safe for panel installation — no additional enclosure required inside a standard IP54 cabinet. Mechanical robustness is specified: the contactor withstands 10 Gn shocks on Y and Z axes (closed) and 4 Gn vibrations at 5-300 Hz (closed), per IEC 60068-2-27 and 60068-2-6. This matters for applications on mobile equipment or near heavy impact sources.

This reversing contactor is sized for DIN-rail mounting in a control panel. The preassembled reversing busbar eliminates the need for external cross-wiring between the two contactors, reducing wiring errors and panel build time. Rated operational voltage on the power circuit is 690 V AC 50/60 Hz, so it can be used on 400 V or 480 V systems with headroom. Operating altitude is 2000 m without derating, covering most installations below that elevation.

Frequently asked questions

What is the closest alternative to the LC2K1610P72 in the TeSys K family?

Within the TeSys K range, the standard (non-reversing) equivalent is the LC1K1610P7. The reversing version adds the mechanical interlock and preassembled busbar. For a different coil voltage, the same contactor frame is available with 24 V AC, 48 V AC, 110 V AC, or 230 V DC coils — the P72 suffix designates the 230 V AC coil.

What compliance documentation does Schneider provide for the LC2K1610P72?

The contactor carries flame retardance ratings of V1 per UL 94 and meets NF F 16-101 and NF F 16-102 requirements. Protective treatment conforms to IEC 60068 and DIN 50016. The IP20 rating is per VDE 0106. Standard Schneider documentation includes the declaration of conformity for CE, UKCA, and EAC as applicable.