Skip to main content
Schneider Electric LC3D115E7 — Contactors

Schneider LC3D115E7 TeSys D Star Delta Starter, 115 A, 48 V

MPNLC3D115E7
Active

Schneider Electric TeSys D star delta starter, 3 x 3P (3 NO), 115 A, 48 V AC coil, AC-3 motor control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC3D115E7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3D115E7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3
LC3D115E7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3D115E7 — Environmental
ParameterValue
IP degree of protectionIP2X front face conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 6 Gn for 11 ms
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94

Product details

The LC3D115E7 is a TeSys D star delta starter from Schneider Electric, designed for motor control applications under AC-3 utilisation category. It is a pre-wired assembly with 3 x 3P (3 NO) power poles, rated at 115 A with a 48 V AC coil. This configuration is used to reduce inrush current during motor start-up by first connecting the motor windings in star configuration, then transitioning to delta for full-load running.

The 115 A rating under AC-3 duty means this starter is sized for switching squirrel-cage induction motors where the making current is typically 5–8 times the rated current, but breaking current is low — the contactor only interrupts the motor's running current, not the start surge. For a 400 V three-phase supply, 115 A AC-3 corresponds roughly to a 55 kW motor, though exact sizing depends on the motor's full-load current and duty cycle. The 48 V AC coil is a low-voltage control circuit standard, common in panels where safety extra-low voltage (SELV) is not required but a lower control voltage reduces shock risk and allows smaller control transformers. Coil pickup and dropout characteristics follow the TeSys D family curve — verify the control transformer can deliver the inrush VA at 48 V. Rated operational voltage is specified for the power circuit, and the signalling circuit is tested to 10 MOhm insulation resistance. The starter operates without derating up to 3000 m altitude, which covers most industrial sites outside high-altitude mining or mountain installations.

Mechanical and environmental robustness

The starter withstands vibrations of 2 Gn (5–300 Hz) when open and 4 Gn when closed, with shock resistance of 15 Gn for 11 ms when closed and 6 Gn for 11 ms when open. Protective treatment TH conforming to IEC 60068-2-30 indicates the starter is tested for damp heat cyclic conditions, meaning it can tolerate high-humidity environments common in food processing or textile plants without corrosion or insulation degradation.

Frequently asked questions

What is the operating temperature range and altitude rating?

Operating ambient temperature is -40 to 70 °C at rated coil voltage, with storage from -60 to 80 °C. The starter operates without derating up to 3000 m altitude.

MPN
LC3D115E7