It switches three power poles in a 3 x 3P NO configuration, rated at 150 A in AC-3 utilisation category, which means it handles the high inrush of squirrel-cage induction motors during start-up and transitions to delta-run without contactor welding. The 24 V AC coil suits control transformers common in panel builds.
This is a panel-mounted star delta starter, pre-wired to reduce installation time. The 3 x 3P NO pole arrangement covers the line and delta contactors in a standard star-delta circuit; the star contactor is typically the third pole set. Operating altitude is rated to 3000 m without derating, covering most high-altitude plant sites. Ambient operating range is -40 to 60 °C, with derating above 60 °C up to 70 °C. Storage range extends from -60 to 80 °C. Mechanical robustness is specified at 2 Gn vibration contactor open, 4 Gn closed, and shock ratings of 15 Gn closed for 11 ms — sufficient for most industrial machinery and conveyor lines.
These ratings satisfy most panel builder and machinery safety audits without additional fire barriers.
The AC-3 rating at 150 A is the motor-switching current, not the resistive (AC-1) rating. For a star-delta starter, the line and delta contactors each see roughly 58% of motor full-load current; this unit handles motors up to about 260 A FLC in star-delta configuration. The 24 V AC coil draw is typical for the TeSys D range — verify the control transformer VA budget includes coil inrush. Protective treatment TH per IEC 60068-2-30 means the unit is tested for damp heat cyclic conditions, suitable for non-condensing humidity in temperate climates. No additional tropicalisation needed for standard indoor panels.