Skip to main content
Schneider Electric LC3D150V7 — Contactors

Schneider TeSys D LC3D150V7 Star Delta Starter, 150 A, 400 V

MPNLC3D150V7
Active

Schneider Electric TeSys D, star-delta starter, 3 x 3P (3 NO) power poles, 150 A, 400 V AC coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC3D150V7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3D150V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3
LC3D150V7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3D150V7 — Environmental
ParameterValue
Operating altitude3000 m
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 6 Gn for 11 ms
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
LC3D150V7 — Other specifications
ParameterValue
Pollution degree3
Device short nameLC3D
Device presentationPre-wired
Power pole contact composition3 x 3 NO
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-40...60 °C 60...70 °C with derating

Product details

The coil is 400 V AC, so it pulls in directly from a standard 400 V three-phase control supply without a separate transformer.

This is a pre-wired assembly, so it lands in the enclosure as a single unit — no on-site wiring between the main and delta contactors. The TeSys D range snaps onto DIN rail or mounts with screws, and the 3 x 3P pole arrangement gives you three NO contacts per phase for the star, delta, and line contactors.

Mechanical robustness for conveyor and material handling lines

Vibration resistance is 2 Gn (5-300 Hz) with the contactor open and 4 Gn (5-300 Hz) closed. Shock resistance is 6 Gn for 11 ms open, 15 Gn for 11 ms closed. That's enough to keep the starter from dropping out on a conveyor line with moderate vibration from motor-roller drives or divert mechanisms.

Frequently asked questions

What is the LC3D150V7's utilisation category and what does that mean for motor switching?

It is rated AC-3, which covers starting, plugging, and inching of squirrel-cage induction motors. At 150 A AC-3, it handles the locked-rotor current of a motor up to roughly 75 kW at 400 V (typical rule of thumb: 2 A per kW for AC-3).

What compliance documentation is available for this part?

The part carries UL 94 V1 flame retardance and IEC 60695-2-1 fire resistance at 850 °C. Protective treatment is TH per IEC 60068-2-30. Standard Schneider documentation includes the RoHS and REACH declarations available through the product support portal.

What operating temperature range does the LC3D150V7 support?

Storage range is -60 to 80 °C. Operating range is -40 to 60 °C, with derating required from 60 to 70 °C.

MPN