Skip to main content
Schneider Electric LC3F225E7A64 — Contactors

Schneider TeSys F LC3F225E7A64 Star Delta Starter, 225 A

MPNLC3F225E7A64
Obsolete

Schneider Electric TeSys F LC3F225E7A64, pre-wired star delta starter, 225 A rated operational current, 200 kW at 400 V AC, 48 V AC 50/60 Hz coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC3F225E7A64 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3F225E7A64 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3
LC3F225E7A64 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3F225E7A64 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 7 Gn for 11 ms
Protective treatment / pollution degreeTH
LC3F225E7A64 — Approvals
ParameterValue
StandardsIEC 60947-4-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1
LC3F225E7A64 — Mechanical
ParameterValue
Width525 mm
Height110 mm
Depth235 mm

Product details

The Schneider Electric TeSys F LC3F225E7A64 is a pre-wired star delta starter designed for motor control applications. It integrates three contactors with mechanical interlocking into a single unit, reducing panel wiring and commissioning time. The unit is rated for AC-3 utilisation category, meaning it is built for switching squirrel-cage motors during starting, running, and stopping — the standard duty for motor starters. Rated operational current is 225 A at up to 440 V AC for the power circuit, which translates to motor power ratings of 200 kW at 380/400 V AC and 220 kW at 440 V AC. The control circuit operates on 48 V AC at 50/60 Hz, with a pickup range of 0.85 to 1.1 Uc and dropout between 0.35 and 0.55 Uc. This 48 V coil is a common choice for control transformers in industrial panels, keeping the control voltage at a safer level than line voltage.

The LC3F225E7A64 carries a rated breaking capacity of 1800 A and a rated making capacity of 2250 A, both conforming to IEC 60947-4-1. The associated fuse recommendation is 315 A gG or 250 A aM at up to 440 V, which is the fuse size the manufacturer expects for short-circuit protection. For a star delta starter, the operating time is 20 to 35 ms for closing and 7 to 15 ms for opening, with a starting time of 30 s — this is the transition delay between star and delta configurations. The unit is plate-mounted (not DIN rail), so factor in panel space for the 525 mm width, 110 mm height, and 235 mm depth. Rated insulation voltage is 1000 V per IEC 60947-4-1, with an operating altitude of 3000 m without derating. The TH protective treatment indicates the unit is tropicalised for humid environments.

The LC3F225E7A64 comes pre-wired with three contactors: KM1 (star), KM2 (line), and KM3 (delta). Auxiliary contact composition is 1 NC + 1 NO for the star contactor, 2 NC + 1 NO for the line contactor, and 1 NC + 2 NO for the delta contactor — enough for status feedback and interlocking without adding external aux blocks. Power connections are via bolted busbars (32 x 4 mm cross-section) or ring terminals up to 185 mm², with an M10 bolt diameter. Control circuit terminals are screw clamp, accepting 1 to 4 mm² solid or flexible wire. Tightening torque is 1.2 N·m for control circuit terminals and 35 N·m for power circuit connections — the power terminations require a torque wrench to avoid high-resistance joints. Heat dissipation is 18 to 24 W, which should be factored into panel thermal calculations, especially in a sealed enclosure.

Frequently asked questions

What are the key ratings for this star delta starter?

Rated operational current is 225 A at up to 440 V AC in AC-3 duty. Motor power is 200 kW at 400 V AC and 220 kW at 440 V AC. The control circuit is 48 V AC 50/60 Hz. Breaking capacity is 1800 A, making capacity is 2250 A, and mechanical durability is 10 million cycles.

What standards does the LC3F225E7A64 comply with?

It conforms to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, JIS C8201-4-1, and EN 60947-1. The IP20 front face protection is per IEC 60529 and VDE 0106.

How is the LC3F225E7A64 mounted and what are its dimensions?

It is plate-mounted (not DIN rail). Dimensions are 525 mm width, 110 mm height, and 235 mm depth. Power connections use M10 bolts with busbar cross-section of 32 x 4 mm or ring terminals up to 185 mm².

What is the auxiliary contact configuration on this starter?

The pre-wired unit includes: 1 NC + 1 NO for the KM1 star contactor, 2 NC + 1 NO for the KM2 line contactor, and 1 NC + 2 NO for the KM3 delta contactor. This provides feedback and interlocking without additional aux blocks.

MPN