Skip to main content
Schneider Electric LC3F225FE7 — Contactors

Schneider Electric LC3F225FE7 TeSys F Star Delta Starter, 22

MPNLC3F225FE7
Obsolete

Schneider Electric TeSys F LC3F225FE7, pre-wired star delta starter, 225 A AC-3 rated operational current, 115 V AC 50/60 Hz control circuit, 3 x 3P poles, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC3F225FE7 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3F225FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3
LC3F225FE7 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3F225FE7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 7 Gn for 11 ms
Protective treatment / pollution degreeTH
LC3F225FE7 — Approvals
ParameterValue
StandardsEN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-1 IEC 60947-4-1
LC3F225FE7 — Mechanical
ParameterValue
Width525 mm
Height110 mm
Depth235 mm

Product details

The Schneider Electric LC3F225FE7 is a pre-wired TeSys F star delta starter, purpose-built for motor control applications. It integrates three contactors (KM1 star, KM2 line, KM3 delta) with the necessary interlocking and timing, so you don't have to wire and coordinate individual components. It delivers 200 kW at 380/400 V AC and 220 kW at 440 V AC, making it a fit for medium-to-large motor loads in pumps, compressors, and conveyors.

The 225 A rated operational current (Ie) at ≤ 440 V AC in AC-3 is the headline number for motor duty. AC-3 covers starting and switching off squirrel-cage motors under load, so this rating directly governs the motor FLA it can handle. The associated fuse recommendation of 315 A gG or 250 A aM at ≤ 440 V provides the short-circuit protection coordination — the starter clears faults up to 1800 A breaking capacity per IEC 60947-4-1, and makes 2250 A. The control circuit is 115 V AC 50/60 Hz, with an operational voltage range of 0.85 to 1.1 Uc and a drop-out range of 0.35 to 0.55 Uc, so it holds in during brownouts but drops reliably when the coil loses power. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 Group C, giving headroom for 690 V systems.

Mounting is on a plate (not DIN rail), so plan for bolt-down installation. The power circuit uses M10 bolted connections or lugs/ring terminals up to 185 mm², with a tightening torque of 35 N.m. The control circuit uses screw clamp terminals accepting 1 to 4 mm² flexible or solid cable, torqued to 1.2 N.m. The auxiliary contact composition is already wired: 1 NC + 1 NO for the star contactor (KM1), 2 NC + 1 NO for the line contactor (KM2), and 1 NC + 2 NO for the delta contactor (KM3). That covers the standard interlocking and status feedback without adding external aux blocks.

Frequently asked questions

What are the key ratings for this star delta starter?

The LC3F225FE7 is rated at 225 A operational current in AC-3 at ≤ 440 V AC, with a control circuit voltage of 115 V AC 50/60 Hz. It delivers 200 kW at 380/400 V AC and 220 kW at 440 V AC. The rated breaking capacity is 1800 A, and the rated making capacity is 2250 A, both per IEC 60947-4-1.

What compliance standards does the LC3F225FE7 meet?

It complies with EN 60947-1, EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, and JIS C8201-4-1. The front face is IP20 per IEC 60529 and VDE 0106. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 Group C.

What is the depth of the LC3F225FE7?

The depth is 235 mm. Width is 525 mm, and height is 110 mm.

MPN
LC3F225FE7