Skip to main content
Schneider Electric LC4D09AB7 — Motor Starters

TeSys LC4D09AB7 DOL Starter, 9A, 24V AC Coil, Obsolete

MPNLC4D09AB7
Obsolete

Schneider Electric TeSys LC4 series DOL starter, LC4D09AB7, 9 A rated operational current (AC-3), 24 V AC 50/60 Hz coil, 4 kW motor power at 400 V, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC4D09AB7 — Mechanical & Connection
ParameterValue
Width86 mm
Height173 mm
Depth98 mm
LC4D09AB7 — Other specifications
ParameterValue
Motor power4 kW at 380...400 V AC 50/60 Hz 4 kW at 415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz
Mounting supportPlate
Range of productTeSys
Device short nameLC4
Device compositionContactor Fuse disconnector
Utilisation categoryAC-3
Product or component typeDOL starter
[Ie] rated operational current9 A
[Ue] rated operational voltage24 V AC 50/60 Hz

Product details

The Schneider Electric TeSys LC4D09AB7 is a direct-on-line (DOL) starter combining a contactor and fuse-disconnector in one unit, rated for 9 A in AC-3 utilisation category — the motor-switching duty class that governs inductive loads like pumps, fans, and small conveyors. Motor power capability spans 4 kW at 380...400 V AC, 4 kW at 415 V, 4 kW at 440 V, 2.2 kW at 220...230 V, and 5.5 kW at 660...690 V — so for a 4 kW motor on a 400 V line this starter is correctly sized without oversizing the contactor. Mounting is plate-mount only — no DIN-rail clip, so factor in a backplate or sub-panel for installation.

Lifecycle reality — obsolete, but available

No direct manufacturer successor part number is listed in the lifecycle record, so a like-for-like drop-in replacement from Schneider is not formally designated — the buyer's path is surplus or independent-distributor stock. Condition is typically new-in-box or new-surplus from cancelled projects or overstock.

The 9 A AC-3 rating is the load-bearing figure for motor starting — it governs the contactor's ability to handle the inrush and break the running current under inductive load. For resistive loads (AC-1) the same contactor would carry a higher current, but AC-3 is the number that decides motor fit. Coil voltage is 24 V AC, not DC — if your control system runs 24 VDC, this coil will not hold in. Physical envelope: 86 mm wide, 173 mm tall, 98 mm deep — plate-mount only, so panel layout must allow for screw-fixing rather than snapping onto a DIN rail.

Frequently asked questions

What is the replacement for LC4D09AB7?

No official Schneider replacement order code is listed for the LC4D09AB7. For a BOM that specifies this exact part, the sourcing path is through independent distributors who carry new-old-stock or surplus units. Availability and pricing are confirmed at quote time against an RFQ.

Where can I buy LC4D09AB7 available via RFQ confirmation?

The LC4D09AB7 is sourced to order through independent distribution against an RFQ.

MPN
LC4D09AB7