Skip to main content
Schneider Electric LC4D12AFE7 — Motor Starters

TeSys LC4D12AFE7 DOL Starter, 16 A AC-3, 48 V AC Coil

MPNLC4D12AFE7
Active

Schneider Electric TeSys LC4 series DOL starter, LC4D12AFE7, 16 A rated operational current (AC-3), 48 V AC 50/60 Hz coil, plate-mounted, active production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC4D12AFE7 — Mechanical & Connection
ParameterValue
Width86 mm
Height173 mm
Depth98 mm
LC4D12AFE7 — Other specifications
ParameterValue
Motor power3 kW at 220...230 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 5.5 kW at 380...400 V AC 50/60 Hz 5.5 kW at 415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz
Mounting supportPlate
Range of productTeSys
Device short nameLC4
Device compositionContactor Fuse disconnector
Utilisation categoryAC-3
Product or component typeDOL starter
[Ie] rated operational current16 A
[Ue] rated operational voltage48 V AC 50/60 Hz

Product details

The LC4D12AFE7 is a direct-on-line (DOL) starter from the TeSys LC4 series, combining a contactor and fuse disconnector in one unit. Its 16 A rated operational current under AC-3 utilisation category tells you it's sized for squirrel-cage motor switching — AC-3 covers starting and plugging, where the current peaks at start and drops to the rated load. The coil pulls in at 48 V AC 50/60 Hz, so verify your control voltage matches before panel wiring. Motor power capability varies with line voltage: 3 kW at 220–230 V, 5.5 kW at 380–400 V / 415 V / 440 V, and 7.5 kW at 500 V. That spread means the same starter covers a 3-phase motor across common European and North American supply voltages, but the actual kW delivered depends on your local mains — size the motor to the voltage column that matches your plant. Mounting is plate-style (not DIN rail), so plan for a backplate or sub-panel with drilled holes — the 173 mm height, 86 mm width, and 98 mm depth define the footprint for enclosure layout.

Frequently asked questions

Does LC4D12AFE7 include an overload relay?

No. The LC4D12AFE7 is a DOL starter combining a contactor and fuse disconnector — it does not include a separate overload relay. An external thermal or electronic overload relay must be added in series for motor protection.

Can LC4D12AFE7 be used with 3-phase motors?

Yes. The motor power ratings are given for three-phase supplies: 3 kW at 220–230 V, 5.5 kW at 380–400 V / 415 V / 440 V, and 7.5 kW at 500 V, all at 50/60 Hz. Wire the motor to the voltage column matching your line.

What is the mounting type for LC4D12AFE7?

Plate mounting — not DIN rail. The footprint is 173 mm high, 86 mm wide, 98 mm deep. Plan for a backplate or sub-panel with drilled fixing points.

MPN
LC4D12AFE7