Skip to main content
Schneider Electric LC4D18AM7 — Motor Starters

TeSys LC4D18AM7 DOL Starter, 18 A, 220 V AC Coil

MPNLC4D18AM7
Active

Schneider Electric TeSys LC4-D DOL starter, 18 A rated operational current, AC-3 utilisation category, coil 220 V AC, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC4D18AM7 — Mechanical & Connection
ParameterValue
Width86 mm
Height173 mm
Depth98 mm
LC4D18AM7 — Other specifications
ParameterValue
Motor power10 kW at 500 V AC 50/60 Hz 4 kW at 220...230 V AC 50/60 Hz 9 kW at 415 V AC 50/60 Hz 9 kW at 440 V AC 50/60 Hz 7.5 kW at 380...400 V AC 50/60 Hz
Mounting supportPlate
Range of productTeSys
Device short nameLC4
Device compositionContactor Fuse disconnector
Utilisation categoryAC-3
Product or component typeDOL starter
[Ie] rated operational current18 A
[Ue] rated operational voltage220 V AC 50/60 Hz

Product details

The LC4D18AM7 is a TeSys DOL starter combining a contactor and fuse disconnector in one unit, rated 18 A in AC-3 duty — the motor-switching category that governs starting and stopping of squirrel-cage induction motors. At 18 A AC-3, it directly handles a 7.5 kW motor at 380–400 V AC or 9 kW at 415/440 V AC, and 10 kW at 500 V AC. The 220 V AC coil matches common control-voltage rails in European panel designs. Plate-mount construction (173 mm tall, 86 mm wide, 98 mm deep) means it bolts to a backplate rather than snapping onto DIN rail — factor that into enclosure layout and gland-plate clearance.

Integration note for panel builders

The plate-mount footprint (86 x 173 mm) and 98 mm depth leave room for side-by-side grouping on the backplate, but the fuse-disconnector section adds height compared to a bare contactor — verify clearance to the enclosure door or busbar shroud before laying out the gland plate.

Frequently asked questions

What is the LC4D18AM7 rated operational current?

The LC4D18AM7 is rated 18 A in AC-3 utilisation category, suitable for direct-on-line starting of induction motors up to 7.5 kW at 380–400 V AC.

Where can I buy the LC4D18AM7?

Sourced to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the LC4D18AM7's mounting style?

Plate-mount — 173 mm tall, 86 mm wide, 98 mm deep. No DIN-rail clip; bolts directly to the enclosure backplate.

MPN
LC4D18AM7