The TeSys LC4D65E7 is a direct-on-line (DOL) starter combining a contactor and fuse disconnector on a single mounting plate — a space-saving unit for controlling three-phase induction motors up to 37 kW at 415 V AC. The 65 A rated operational current (Ie) in AC-3 utilisation category means it switches motor loads under starting and running conditions, not just resistive heating. At 380-400 V AC it handles 30 kW; at 415-690 V AC it handles 37 kW. The 48 V AC coil voltage is worth noting — this is a low-voltage control coil, common in safety or PLC-driven circuits where 48 V control power is already available.
Plate-mounted — the 281 mm width, 130 mm depth, and 143 mm height define the footprint for panel layout. No DIN-rail clip here; it bolts directly to a backplate. Verify the 48 V AC control transformer sizing against the coil inrush before wiring.