Skip to main content
Schneider Electric LE4D09R7 — Overload Relays

Schneider Electric LE4D09R7 TeSys LE Enclosed DOL Starter, 9

MPNLE4D09R7
Obsolete

Schneider Electric TeSys LE series, LE4D09R7, enclosed DOL starter, 9 A Ith, 440 V AC coil, IP65, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LE4D09R7 — Mechanical
ParameterValue
Width186 mm
Height330 mm
Depth175.5 mm

Product details

The Schneider Electric LE4D09R7 is an enclosed direct-on-line (DOL) starter from the TeSys LE range, rated for standard motor starting duty. Rated at 9 A conventional free-air thermal current (Ith) and 4 kW at 380/400 V AC in utilisation category AC-3, this starter handles the switching of squirrel-cage induction motors up to that power level. The AC-3 rating means it's designed for starting motors and disconnecting them only after they've stopped — not for inching or plugging duty. The unit accepts cable entries from ISO20 through ISO40 sizes on both top and bottom faces.

Designed to IEC 60947-4-1, the standard for contactors and motor-starters. The IP65 and IK07 ratings confirm suitability for dust-tight, hose-down environments with mechanical impact resistance up to 2 J. The associated fuse rating is 12 A, 10 x 38 mm aM type — a gG or aM fuse of that size provides the short-circuit backup.

Frequently asked questions

What is the closest alternative to the LE4D09R7 in the TeSys family?

No official successor is listed. For a functionally similar enclosed DOL starter in the current TeSys range, you would need to evaluate a current TeSys LE or TeSys island starter against your specific voltage, current, and enclosure requirements — the LE4D09R7 has no direct pin-compatible drop-in replacement.

What are the key ratings of the LE4D09R7?

9 A conventional free-air thermal current (Ith), 4 kW motor power at 380/400 V AC in AC-3 duty, 440 V AC control coil voltage, IP65 enclosure protection, and IK07 impact resistance.

What compliance standards does the LE4D09R7 meet?

It is designed to IEC 60947-4-1 for contactors and motor-starters. The IP65 and IK07 ratings are per IEC 60529.

MPN
LE4D09R7