Skip to main content
Schneider Electric LE4D18V7A05 — Overload Relays

Schneider Electric LE4D18V7A05 TeSys LE Enclosed DOL Starter

MPNLE4D18V7A05
Obsolete

Schneider Electric TeSys LE, enclosed DOL starter, 18 A, 400 V AC coil, push-button reset, IP65, polycarbonate enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LE4D18V7A05 — Mechanical
ParameterValue
Width186 mm
Height330 mm
Depth175.5 mm

Product details

It ships as a complete unit with a 400 V AC coil, push-button reset, and an IP65 polycarbonate enclosure — ready for standalone mounting in washdown or dusty environments.

The 18 A thermal current (Ith) is the continuous rating in open air; for motor duty, the AC-3 category governs switching of squirrel-cage motors during starting and plugging. The motor power table covers 4 kW at 220/230 V AC up to 10 kW at 500 V AC — the 9 kW at 415 V AC and 7.5 kW at 380/400 V AC are the most common European line voltages. The 400 V AC coil matches standard three-phase control circuits without a separate transformer.

Cable entries are provided top and bottom for ISO20, ISO25, ISO32, and ISO40 glands, giving flexibility for incoming supply and outgoing motor cables. The device composition requires a separately ordered thermal overload relay and a contactor fuse disconnector; the enclosure is pre-drilled for these components. The associated fuse rating is 20 A aM (10 x 38 mm) for short-circuit protection.

Frequently asked questions

What are the key ratings for this enclosed DOL starter?

The LE4D18V7A05 is rated 18 A conventional free-air thermal current (Ith), AC-3 utilisation category, with a 400 V AC coil. Motor power ranges from 4 kW at 220/230 V to 10 kW at 500 V AC. Enclosure is IP65 with IK07 impact protection.

What standards does the LE4D18V7A05 comply with?

It complies with IEC 60947-4-1 for contactors and motor-starters. The IP65 and IK07 ratings are per IEC 60529.

How do I source this obsolete part?

Since it is obsolete, sourcing is via surplus inventory or broker networks. Submit an RFQ for a quote on available stock; lead time and price depend on channel inventory at time of request.