Rated at 25 A conventional free-air thermal current (Ith) and AC-3 utilisation category, it handles motor loads up to 11 kW at 380/400/415/440 V AC and 15 kW at 500 V AC — covering standard three-phase induction motors in that power band.
Deployment context
IP65 and IK07 protection let this starter live on the machine frame in washdown areas, outdoors under a roof, or on a plant wall — no separate enclosure needed. Cable entries on top and bottom accept ISO20 through ISO40 glands, so it's ready for standard armoured or flexible conduit runs. The polycarbonate body is tough enough for most industrial environments but keep it out of direct solvent spray; it's rated for -5 to 40 °C ambient.
Lifecycle reality
No direct official successor order code is published in the available records.
The 25 A Ith rating is the thermal current in open air — the continuous current the starter's power path can carry without exceeding temperature rise limits. Associated fuse rating of 25 A aM (10 x 38 mm) gives short-circuit protection coordinated with the starter — the aM characteristic handles motor inrush without nuisance blowing while clearing faults fast enough to protect the contactor. Built to IEC 60947-4-1, the standard for contactors and motor-starters. That covers the whole assembly — contactor, overload (ordered separately), and enclosure — as a coordinated unit.