Skip to main content
Schneider Electric LG1D182M721 — Motor Starters

TeSys LG1D182M721 Enclosed DOL Starter, 17…23 A, 220 V AC

MPNLG1D182M721
Obsolete

Schneider Electric TeSys LG enclosed DOL starter, LG1D182M721, 17…23 A thermal adjustment, 220 V AC 50/60 Hz coil, IP55, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LG1D182M721 — Mechanical & Connection
ParameterValue
Width175 mm
Height165 mm
Depth165 mm

Product details

The LG1D182M721 is an enclosed direct-on-line starter from the TeSys LG range, combining a contactor, switch disconnector, and circuit-breaker in one IP55 polycarbonate enclosure. It is rated for AC-3 motor duty, with thermal protection adjustable from 17 to 23 A and a 220 V AC 50/60 Hz control coil. Motor power ratings: 4 kW at 220/230 V AC, 9 kW at 400/415 V AC, and 9 kW at 440 V AC — all at 50/60 Hz. The enclosure carries an IK07 impact rating and meets IEC 60204-1 and IEC 60947-4-1 standards for safety and motor-starter performance.

The 17…23 A thermal adjustment range sets the overload relay trip band. For a motor with a nameplate full-load current of, say, 19 A, this starter dials in directly. The AC-3 rating (IEC 60947-4-1) confirms it is designed for starting squirrel-cage motors — switching under load, not just isolating. IP55 means the enclosure is dust-protected and hose-down resistant, suitable for washdown areas or outdoor installation under a canopy. The IK07 impact rating (2 Joules) handles light mechanical knocks from tools or debris. Cable entry: four knockouts on top and bottom — two Pg 13 and two Pg 16 per face — give flexibility for incoming supply and motor leads without drilling the polycarbonate.

Deployment context

This is a self-contained safety starter for a motor branch circuit. The integrated switch disconnector provides visible-break isolation for lockout/tagout; the circuit-breaker handles short-circuit protection; the contactor and overload relay manage normal starting and running. The push-button controls (white start, black stop, red rotary emergency stop) are built into the enclosure lid, so no separate control station is needed at the machine.

Frequently asked questions

Where can I buy LG1D182M721?

The LG1D182M721 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of LG1D182M721?

The LG1D182M721 is an enclosed DOL starter with thermal protection adjustable 17…23 A, a 220 V AC 50/60 Hz coil, IP55 enclosure, and AC-3 utilization category. It delivers 4 kW at 220/230 V AC and 9 kW at 400/415 V AC or 440 V AC.

What standards does LG1D182M721 comply with?

It complies with IEC 60204-1 (safety of machinery) and IEC 60947-4-1 (contactors and motor-starters). The enclosure meets IP55 per IEC 60529 and IK07 per IEC 60529.

MPN
LG1D182M721