The Schneider LG1K065M7 is an enclosed direct-on-line (DOL) starter from the TeSys LG range, combining a switch disconnector, a contactor, and provision for a circuit breaker (ordered separately) in a single polycarbonate enclosure. It is rated for 6 A in AC-3 duty (motor switching) with a 220/230 V AC 50/60 Hz control coil. The IP55 and IK07 ratings mean it withstands water jets and 2 J impact — suitable for washdown or light industrial environments where the starter needs to be mounted near the motor, not locked in a clean panel. The enclosure measures 175 mm wide by 165 mm high by 165 mm deep, with cable entries: 4 × Pg 13 + 2 × Pg 16 at top and bottom. The control interface includes a white push-button start, a black push-button stop, and a red rotary emergency stop handle.
This part is obsolete per the manufacturer. The AC-3 rating of 6 A at 400 V (implied by the standard IEC 60947-4-1) means it switches a motor load up to roughly 3 kW at 400 V three-phase. If your motor is larger, or if you need a different coil voltage, the obsolete status means you will be looking at a replacement from the current TeSys range — verify the mounting footprint and gland positions against the original panel cutout.
The LG1K065M7 complies with IEC 60204-1 (safety of machinery — electrical equipment) and IEC 60947-4-1 (contactors and motor-starters). The IP55 enclosure and IK07 impact resistance are certified to IEC 60529.