The LG1K065M704 is a Schneider Electric TeSys LG enclosed direct-on-line (DOL) starter — a self-contained motor-starting package that combines a contactor, switch-disconnector, and circuit-breaker in one polycarbonate enclosure. It's rated for AC-3 duty (motor switching) and thermally adjustable from 0.40 to 0.63 A, which maps to a 0.18 kW motor at 400/415 V AC or 440 V AC, 50/60 Hz.
The thermal protection adjustment range of 0.40...0.63 A sets the overload relay's trip curve — you set it to the motor's full-load current within that window. The 0.18 kW motor power at 400/415 V gives a quick sizing check: if your motor nameplate is 0.18 kW at those voltages, this starter is electrically matched. Control interface is built in: a white push-button for start, a black push-button for stop, and a red rotary-handle emergency stop. Cable entries are 4 x Pg13 + 2 x Pg16 at both top and bottom, giving flexibility for incoming and outgoing cables.
Designed to IEC 60947-4-1 (contactors and motor-starters) and IEC 60204-1 (safety of machinery — electrical equipment). The safety application tag indicates use in machine safety circuits.