Skip to main content
Schneider Electric LG1K065P706 — Motor Starters

LG1K065P706 TeSys LG Enclosed DOL Starter, 1...1.6 A

MPNLG1K065P706
Active

Schneider Electric TeSys LG series, LG1K065P706, enclosed DOL starter, 1...1.6 A thermal protection range, 230 V AC 50/60 Hz coil, IP55, IK07, AC-3 utilisation category.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LG1K065P706 — Mechanical & Connection
ParameterValue
Width175 mm
Height165 mm
Depth165 mm

Product details

Integrator note — what this box does on the line

The LG1K065P706 is a fully enclosed direct-on-line (DOL) starter from the TeSys LG family, integrating a contactor, switch disconnector, and circuit-breaker in a single polycarbonate enclosure rated IP55 and IK07. It is designed for standard-environment safety applications (IEC 60947-4-1, IEC 60204-1) where you need a compact, pre-wired motor start/stop station with integrated thermal overload protection. The thermal protection adjustment range is 1...1.6 A, which means it directly protects small motors — typically 0.25 kW at 220/230 V AC, 0.55 kW at 400/415 V AC, and 0.55 kW at 440 V AC — all at 50/60 Hz. The AC-3 utilisation category confirms it is rated for switching squirrel-cage induction motors under starting and stopping duty. Cable entry is provided by four knockouts: 2 x Pg 13 and 2 x Pg 16 on both top and bottom faces.

Sourcing and lifecycle — active, quoted to order

Because it is an active TeSys LG model, there is no forced replacement or last-time-buy window. For BOM-freeze planning, this part should remain orderable through normal supply routes for the foreseeable future. No official successor order code exists — it is the current generation.

Mounting and integration — enclosure-ready

The polycarbonate enclosure measures 175 mm wide × 165 mm high × 165 mm deep. It is designed for wall or panel mounting in standard environments — no DIN-rail adapter needed. IK07 impact resistance protects against 0.5 J mechanical shocks. Cable entry is pre-punched for 2 x Pg 13 and 2 x Pg 16 glands top and bottom. This gives flexibility for top-entry mains and bottom-entry motor cables, or vice versa. The push-buttons and emergency-stop handle are factory-fitted — no additional panel drilling or component mounting required.

Frequently asked questions

What is the motor power rating for LG1K065P706 at 230V AC?

At 220/230 V AC 50/60 Hz, the LG1K065P706 is rated for 0.25 kW motor power. At 400/415 V AC and 440 V AC, it is rated for 0.55 kW.

Does LG1K065P706 include a circuit breaker and emergency stop?

Yes. The device composition includes a contactor, switch disconnector, and circuit-breaker. The front panel has a push-button start (white I), push-button stop (black O), and a rotary-handle emergency stop (red).

MPN
LG1K065P706