The Schneider Electric TeSys LG1K065V702 is an enclosed direct-on-line (DOL) starter, combining a contactor, switch disconnector, and circuit-breaker in a single IP55 polycarbonate enclosure rated IK07. It is designed for safety applications per IEC 60947-4-1 and IEC 60204-1, providing coordinated motor starting, overload protection, and isolation in a compact package. The thermal protection adjustment range is 0.16...0.25 A, sized for the smallest fractional-horsepower motors — think 0.06 kW at 400/415 V AC or 440 V AC, 50/60 Hz. The control circuit coil is 400 V AC, so the starter is line-voltage controlled without a separate control transformer. The front panel carries a white push-button for start, a black push-button for stop, and a red rotary-handle emergency stop, giving local operator control and an E-stop that satisfies safety-circuit isolation requirements.
Lifecycle status and sourcing reality
No manufacturer lead time applies — this is a last-time-buy or broker-market part.
The 0.16...0.25 A thermal range directly sets the motor full-load current it protects; if your motor nameplate falls outside that window, the starter cannot be field-adjusted to cover it. IP55 with IK07 impact resistance means the enclosure withstands hose-directed water and dust ingress, plus a 0.5 J impact — suitable for washdown areas or floor-mounted locations near the machine, provided ambient conditions stay within standard environmental limits. The polycarbonate material is UV-stable for indoor industrial use but should not be relied on for direct-sunlight outdoor exposure over years. Cable entries are 4 knockouts: 2 x Pg 13 and 2 x Pg 16 at both top and bottom. That gives flexibility for top-entry or bottom-entry conduit runs, but the Pg thread is metric — verify your cable gland compatibility if you are working in an NPT-standard plant.