Skip to main content
Schneider Electric LG1K095N714 — Motor Starters

Schneider TeSys LG1K095N714 Enclosed DOL Starter, 6-10A

MPNLG1K095N714
Obsolete

Schneider Electric TeSys LG enclosed DOL starter, model LG1K095N714, 6-10 A thermal protection, 400/415 V AC coil, IP55, AC-3 rated 4 kW at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LG1K095N714 — Mechanical & Connection
ParameterValue
Width175 mm
Height165 mm
Depth165 mm

Product details

The Schneider Electric LG1K095N714 is an enclosed direct-on-line (DOL) starter from the TeSys LG range, combining a contactor, switch disconnector, and circuit-breaker in a single IP55 polycarbonate enclosure. Rated for AC-3 duty at 4 kW on 400/415 V AC supply (50/60 Hz), it handles motor starting loads up to that power class, with a thermal protection adjustment range of 6 to 10 A. The control circuit operates at 400/415 V AC, and the enclosure carries push-button start (white I), stop (black O), and a rotary emergency-stop handle (red) — a self-contained safety motor-start package for standard environments.

The 6-10 A thermal protection range sets the motor full-load current window this starter can protect — a 4 kW motor at 400 V typically draws around 8-9 A full-load, so the 10 A top end gives headroom but not enough for a 5.5 kW motor (≈11-12 A). IP55 enclosure with IK07 impact resistance makes it suitable for washdown or dusty industrial environments where the starter is mounted directly on the machine frame rather than in a separate control panel.

Integration notes

Dimensions are 175 mm wide × 165 mm deep × 165 mm high — a compact footprint for a self-contained motor starter with integrated controls. Cable entries: four knockouts on top (2 × Pg 13 + 2 × Pg 16) and four on the bottom (same pattern), giving flexibility for top/bottom conduit entry in a wall-mount or machine-mount installation. Compliant with IEC 60947-4-1 (contactors and motor-starters) and IEC 60204-1 (safety of machinery — electrical equipment), so it meets the standard machinery directive requirements for a motor starter in European-classified installations.

Frequently asked questions

What is the replacement for LG1K095N714?

No official successor order code is listed in the manufacturer's lifecycle data for this part. A direct parametric substitute would need to match the 6-10 A thermal range, 400/415 V AC coil, IP55 enclosure, and AC-3 4 kW rating. Confirm the correct cross-reference at quote time when submitting an RFQ.

Where can I buy LG1K095N714?

This obsolete part is sourced through independent industrial-automation distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time, no stock figures carried on this listing.

What motor power does LG1K095N714 handle?

It is rated for 4 kW at 400/415 V AC and 440 V AC (50/60 Hz), and 1.5 kW at 220/230 V AC — all in AC-3 duty (squirrel-cage motor starting).

MPN
LG1K095N714