Schneider Electric LG1K095Q714A37 — Motor Starters

Schneider LG1K095Q714A37 TeSys LG Enclosed DOL Starter

MPNLG1K095Q714A37
Active

Schneider TeSys LG enclosed DOL starter, LG1K095Q714A37, 6-10 A thermal protection, 380/400 V AC coil, 4 kW at 400 V AC-3, IP55 polycarbonate enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LG1K095Q714A37 — Mechanical & Connection
ParameterValue
Width175 mm
Height165 mm
Depth165 mm

Product details

Enclosed DOL starter for 4 kW motor duty

The Schneider LG1K095Q714A37 is a TeSys LG enclosed direct-on-line starter rated for 4 kW at 400/415 V AC 50/60 Hz in AC-3 utilisation category, meaning it handles the starting and stopping of standard three-phase squirrel-cage induction motors up to that power without external contactor or overload assembly. The 380/400 V AC 50/60 Hz control circuit voltage means the coil energises directly from a standard 400 V three-phase control supply; no step-down transformer or separate control voltage is needed for the starter's own operation.

Built-in components and enclosure

This enclosed starter integrates a contactor, a switch disconnector, and a circuit-breaker in one IP55 polycarbonate enclosure rated IK07 for impact resistance — suitable for wall-mounting in industrial environments where washdown or dust ingress is a concern. The control interface includes a white push-button for start, a black push-button for stop, and a red rotary handle for emergency stop plus a red mushroom-head emergency stop push-button, giving operators both a local run/stop station and a lockable emergency stop on the enclosure face. Four cable entries are provided — 2 x Pg 13 and 2 x Pg 16 at both top and bottom — allowing incoming supply and outgoing motor cables to be glanded without drilling additional holes.

Standards compliance and lifecycle

The LG1K095Q714A37 is designed to IEC 60204-1 (safety of machinery — electrical equipment) and IEC 60947-4-1 (contactors and motor-starters), so it meets the machinery directive requirements for a motor branch circuit in a CE-marked panel. The product lifecycle status is active, meaning Schneider continues to manufacture this order code without a published end-of-life notice — it remains a current catalog item for new installations and spares restocking.

Frequently asked questions

Is LG1K095Q714A37 suitable for a 4 kW 400 V three-phase motor?

Yes, it is rated for 4 kW at 400/415 V AC 50/60 Hz in AC-3 utilisation category, which covers starting and stopping of a standard three-phase induction motor at that power.

Does LG1K095Q714A37 include an overload relay?

Yes, the enclosed starter includes a circuit-breaker with thermal protection adjustable from 6 to 10 A, which functions as the overload relay for the motor branch.

What is the difference between LG1K095Q714A37 and LG1K095Q714A36?

The LG1K095Q714A37 has a 380/400 V AC coil, while the LG1K095Q714A36 uses a different control voltage — verify the coil voltage on your BOM to select the correct variant.

MPN