The TeSys LG7K06M702A04 is an enclosed direct-on-line starter combining a contactor and a circuit-breaker in a single polycarbonate enclosure, rated for 0.06 kW at 400/415 V AC 50/60 Hz (AC-3 utilisation category). The 220/230 V AC coil and thermal protection adjustable from 0.16 to 0.25 A make it a drop-in safety starter for small motor loads — pumps, fans, conveyors — where a local emergency-stop mushroom head is required. IP55 and IK07 ratings mean the enclosure handles washdown and accidental impacts up to 0.5 J — standard for food-and-bev or light industrial environments where the starter mounts near the machine.
The 0.06 kW motor power at 400/415 V AC is the headline number — this starter is sized for fractional-horsepower motors, not general-purpose 0.75 kW loads. The AC-3 duty class confirms it switches squirrel-cage motors on and off under full load, not just resistive heating. Thermal protection range 0.16...0.25 A matches the motor full-load current for a 0.06 kW 400 V motor. Set the dial to the motor nameplate FLA; the integrated circuit-breaker provides short-circuit and overload protection in one device, eliminating a separate motor-protective breaker.
Safety and compliance
Designed for safety applications per IEC 60947-4-1 and IEC 60204-1, the mushroom-head push-button (red, twist-to-release) provides local emergency stop. The enclosed format meets machine-guarding requirements where exposed live parts are unacceptable.
Integration notes
Polycarbonate enclosure measures 175 mm wide × 165 mm high × 177 mm deep. Cable entries: four knockouts — two Pg 13 and two Pg 16 on top, same on bottom. Mounts directly to a machine frame or panel; no DIN-rail adapter needed.