Enclosed DOL starter for motor control
It is designed for safety applications per IEC 60204-1 and IEC 60947-4-1, with a push-button start (white I), stop (black O), and a red mushroom-head emergency stop. The thermal protection adjustment range is 1...1.6 A, and the control circuit voltage is 400/415 V AC 50/60 Hz. Rated motor power reaches 0.25 kW at 220/230 V AC and 0.55 kW at 400/415 V AC or 440 V AC, all at 50/60 Hz. The utilisation category is AC-3, meaning it is suited for switching squirrel-cage motors — starting, stopping, and inching under load — up to those power levels.
The enclosure measures 175 mm wide by 165 mm high by 177 mm deep, with cable entries: 4 entries (2 x Pg13 + 2 x Pg16) on top and the same on bottom. IK07 impact resistance handles incidental knocks from tools or panels.