The LG7K06N710 is a TeSys LG enclosed direct-on-line starter combining a contactor and circuit-breaker in one IP55 polycarbonate enclosure — a single order code that covers the motor-starting and short-circuit protection for a fixed-speed motor branch. The thermal protection adjustment range of 4 to 6.3 A sets the overload relay trip point, so this starter fits a motor whose full-load current falls inside that window — typically a 2.2 kW motor on a 400/415 V supply, or a 1.1 kW motor on 220/230 V. The 400/415 V AC 50/60 Hz control coil means the starter picks up directly from a 400 V line-to-line signal — no separate control transformer needed in a 400 V panel. Rated for AC-3 utilisation category (IEC 60947-4-1), the contactor is designed for starting and stopping squirrel-cage induction motors — the dominant load type in conveyor, pump, and fan duty.
Deployment context: where this goes and what it guards
The IP55 enclosure and IK07 impact rating make the LG7K06N710 suitable for installation in washdown areas, light industrial environments, or on-machine mounting where dust and water jets are present but high-pressure hose-down is not routine. Cable entries are provided top and bottom — four knockouts per face, sized Pg 13 and Pg 16 — so the starter can be wired into a fixed installation without an additional junction box. The integrated push-button controls (white start, black stop, red mushroom-head emergency stop) mean the starter doubles as a local operator station — no separate push-button enclosure needed for a single-motor cell.