It provides thermal protection adjustable from 0.16 to 0.25 A and is controlled via a white start push button, a black stop push button, and a red mushroom-head emergency stop. The 400 V AC coil matches common European 400/415 V three-phase line voltages.
Lifecycle status and sourcing reality
This part is officially obsolete per the manufacturer. No direct successor order code is listed, so any replacement must be selected based on the same ratings: 0.16–0.25 A thermal protection range, 400 V AC coil, AC-3 motor switching, and IP55 enclosure.
The thermal protection adjustment range of 0.16...0.25 A sets the motor full-load current window — this starter is sized for very small motors (0.06 kW at 400/415 V). The AC-3 utilisation category means it is rated for starting squirrel-cage motors and switching them off during running, not for resistive loads. IP55 protection allows outdoor or washdown-area mounting; the polycarbonate enclosure resists corrosion and impact (IK07). The 400 V AC coil must be fed from a phase-to-phase supply, not a control transformer stepping down to 24 V.