It is rated for AC-3 motor duty at 3 kW on 440 V AC 50/60 Hz supply, with a thermal protection adjustment range of 4...6.3 A.
The 4...6.3 A thermal adjustment range is the setting window for the integrated GV2 motor circuit breaker — you dial it to match the motor full-load current, not the starter's maximum. At 440 V AC the starter handles a 3 kW motor; at 400/415 V it covers 2.2 kW. The AC-3 category means it is rated for starting squirrel-cage motors under load, which is the standard duty for most conveyor, pump, and fan applications. The IP55 enclosure keeps dust and water jets out, so this unit mounts directly on the machine frame or wall in washdown areas — no secondary cabinet needed. The IK07 impact rating means it survives a 0.5 J blow without cracking the polycarbonate cover. If your control circuit runs at 230 V or 24 VDC, this coil voltage will not pick; you need a different TeSys LG variant.
