Skip to main content
Schneider Electric LG7K09B714 — Motor Starters

TeSys LG7K09B714 Enclosed DOL Starter, 6-10 A, 24 V AC

MPNLG7K09B714
Active

Schneider Electric TeSys LG, enclosed DOL starter, 6-10 A thermal protection, 24 V AC coil, IP55 polycarbonate enclosure, 4 kW at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LG7K09B714 — Mechanical & Connection
ParameterValue
Width175 mm
Height165 mm
Depth177 mm

Product details

The Schneider Electric TeSys LG7K09B714 is an enclosed direct-on-line (DOL) starter — a self-contained unit combining a contactor and a circuit-breaker with thermal overload protection, all in a single polycarbonate enclosure. It is designed for starting and stopping three-phase induction motors up to 4 kW at 400/415 V AC 50/60 Hz, with a thermal protection adjustment range of 6 to 10 A. Because it is a DOL starter, it applies full line voltage to the motor terminals during start-up, which is the standard method for smaller motors that do not require reduced-voltage starting.

The AC-3 utilisation category (per IEC 60947-4-1) is the standard rating for squirrel-cage motor starting: switching motors during starting, running, and plugging/reversing. The 4 kW at 400/415 V AC figure is the real-world motor sizing limit in AC-3 duty — do not oversize the motor beyond that even if the thermal range seems to allow it, because the contactor's electrical endurance at AC-3 governs. The unit also complies with IEC 60204-1 (safety of machinery — electrical equipment), which is the standard most machine builders reference for control panels. If your panel runs a 24 V DC control bus, you cannot use this unit without an interposing relay or a separate AC supply for the coil. The push-button controls are integrated: a white start button, a black stop button, and a red mushroom-head emergency stop. The cable entries accept 4 x Pg 13 and 2 x Pg 16 glands at both top and bottom, giving flexibility for top-entry or bottom-entry wiring. Overall dimensions are 175 mm wide, 165 mm high, and 177 mm deep — plan your enclosure backplate layout accordingly.

Frequently asked questions

Where can I buy LG7K09B714 and get a price?

The LG7K09B714 is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the motor power rating for LG7K09B714?

The LG7K09B714 is rated for 4 kW at 400/415 V AC 50/60 Hz, 4 kW at 440 V AC 50/60 Hz, and 1.5 kW at 220/230 V AC 50/60 Hz, all in AC-3 duty.

What is the difference between LG7K09B714 and LG7K09B722?

The primary difference is the control circuit voltage. The LG7K09B714 uses a 24 V AC 50/60 Hz coil, while the LG7K09B722 uses a different coil voltage. Verify the coil voltage on the B722 variant against your control supply before ordering.

Can I use a 24 V DC coil instead of AC on this starter?

No. The LG7K09B714 control circuit is rated for 24 V AC 50/60 Hz only. A 24 V DC supply will not reliably hold the contactor closed. Use an interposing relay or a separate AC supply if your panel runs on DC control voltage.

What is a DOL starter?

A direct-on-line (DOL) starter connects the motor directly to the full supply voltage at start-up. It is the simplest and most economical starting method for smaller motors (typically up to 5-7.5 kW) where high starting current is acceptable. The LG7K09B714 combines the contactor, circuit-breaker, and thermal overload in one enclosed unit.

MPN
LG7K09B714