The LG7K09S714 is a Schneider Electric TeSys LG enclosed direct-on-line (DOL) starter, combining a contactor and circuit-breaker in one IP55 polycarbonate enclosure. It's rated for AC-3 duty at 4 kW on a 400/415 V AC supply, with a thermal protection adjustment range of 6...10 A and a 500 V AC control coil. This is a safety-rated device per IEC 60947-4-1 and IEC 60204-1, with push-button controls including a white start, black stop, and red mushroom-head emergency stop.
The thermal protection range of 6...10 A sets the overload relay trip window; you size the motor full-load current within that band. The 500 V AC coil means the control circuit must supply that voltage — not a standard 24 VDC or 230 V — so verify your panel's control transformer taps. Cable entry is generous: four Pg 13 and two Pg 16 knockouts on both top and bottom faces, giving flexibility for incoming supply and motor leads without extra gland plates.
Deployment context
This is a self-contained DOL starter for individual motor control — mount it on a wall, machine frame, or inside a panel. The polycarbonate enclosure is non-metallic, so no bonding earth lug is required for the enclosure itself, but the internal metal chassis must be earthed per IEC 60204-1. The push-button controls are integrated, so no separate start/stop station is needed for basic operation.